Skip to main content
Schneider Electric ATV1200A23403333 — AC Drive (VFD) 480V

Schneider Electric ATV1200A23403333 AC Drive, 1956 kW

MPNATV1200A23403333
Active

Schneider Electric Altivar 1200 ATV1200A23403333 medium-voltage AC drive, 1956 kW motor power, 2970-3630 V supply, 18-pulse diode rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A23403333 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A23403333 — Power & Output
ParameterValue
Motor power (kW)1956 kW
Continuous output current410 A (standard overload) 328 A (high overload)
Max. transient current492 A for 60 s
Apparent power2340 kVA

Input / Supply

ATV1200A23403333 — Input / Supply
ParameterValue
Rated supply voltage range3.3 kV +/- 10 %
Input line current410 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A23403333 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesSensorless flux vector control Voltage/frequency ratio (V/f) Vector control with sensor, optional Closed-loop control with encoder
Synchronous motor control modesClosed-loop control with encoder Voltage/frequency ratio (V/f)

Protection & EMC

ATV1200A23403333 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A23403333 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP41 IP42 IP31
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A23403333 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A23403333 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A23403333 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

1956 kW medium-voltage drive for synchronous and asynchronous motors

The ATV1200A23403333 is a Schneider Electric Altivar 1200 medium-voltage AC drive rated for 1956 kW motor power with a supply voltage range of 2970-3630 V. It is designed for both synchronous and asynchronous motors, making it suitable for large pump, fan, compressor, and conveyor applications in heavy industry. The 18-pulse diode rectifier input stage reduces line current harmonics compared to a 6- or 12-pulse configuration, which simplifies compliance with IEEE 519 harmonic limits without requiring external filters in many installations.

Overload capability and load profile matching

The drive offers two overload profiles: standard overload at 1.2 In for 60 s and 1.5 In for 3 s, and high overload at 1.5 In for 60 s and 1.85 In for 3 s. This allows matching the drive to the load's duty cycle — standard overload for variable-torque loads like centrifugal pumps and fans, high overload for constant-torque loads like conveyors or extruders that need higher starting torque. The prospective line short-circuit current is rated at 31.5 kA for 150 ms, which defines the upstream protection coordination and the fault-withstand capability of the drive's input section. Dielectric strength between earth and power terminals is 10 kV AC, confirming the medium-voltage isolation design for the 3 kV class supply.

Physical construction and site planning

The drive is supplied in a floor-standing enclosure with separate air flows for the transformer and power cells. Dimensions are 2670 mm high, 4560 mm wide (standard efficiency) or 4860 mm wide (high efficiency), and 1700 mm deep (high efficiency) or 1600 mm deep (standard efficiency). The enclosure colour is grey RAL 7032. Cooling is forced convection with a volume of 23,100 m³/h for both efficiency variants. The noise level is 80 dB, which must be considered for indoor installation near personnel. The operating altitude range is 1000-2000 m with a current derating of 0.6% per 100 m above 1000 m. Pollution degree 2 per EN/IEC 61800-5-1 applies, and the operating position is vertical ±10 degrees.

The drive carries CE marking and complies with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. An integrated EMC filter is included. The lifecycle status is current production.

MPN