Skip to main content
Schneider Electric ATV1200A28001010

Schneider ATV1200A28001010 Medium-Voltage Drive, 2341 kW

MPN ATV1200A28001010
Active

Schneider Electric Altivar 1200 medium-voltage drive, ATV1200A28001010, 2341 kW motor power, 2800 kVA apparent power, 48-pulse diode rectifier input, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV1200A28001010 specifications
ParameterValue
Input type48 pulse diode rectifier bridge
Protection typeGround fault protection: drive
Coil voltage220 V
Current200 A
IP ratingIP41 / IP42 / IP31
Temp storage max60 °C
Temp storage min-10 °C
Temp operating max50 °C
Temp operating min0 °C
Storage temperature-10...60 °C
Pollution degreePollution degree 2
Depth1500 mm (standard efficiency)
Width6870 mm (standard efficiency)
Height2670 mm standard efficiency
Operating positionVertical +/- 10 degree
Operating temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)

Product details

Medium-voltage drive for large asynchronous motors

The ATV1200A28001010 is a Schneider Electric Altivar 1200 medium-voltage drive rated for 2341 kW motor power with 2800 kVA apparent power, designed for large asynchronous motor loads in heavy industrial applications. Input is via a 48-pulse diode rectifier bridge, supplied at 2970...3630 V, drawing 200 A line current with a prospective short-circuit rating of 31.5 kA for 150 ms. The drive is built as a floor-standing enclosure with separate air flows, measuring 1500 mm deep by 6870 mm wide by 2670 mm high — this is a large footprint that requires dedicated floor space and a foundation plan.

Overload and protection capabilities

Standard overload withstand: 1.2 x In for 60 seconds, 1.5 x In for 3 seconds. High overload: 1.5 x In for 60 seconds, 1.85 x In for 3 seconds — this gives flexibility for starting heavy inertia loads without oversizing the drive. Integrated ground fault protection and a dielectric strength of 28 kV AC between earth and power terminals. Pollution degree 2 per EN/IEC 61800-5-1, overvoltage category II. Cooling is forced convection with a volume of 26400 m³/h (standard efficiency). Noise level is 80 dB — ear protection zones are needed near the enclosure.

Composition and control interfaces

The drive comprises 2 plinths, a phase-shifting transformer, medium-voltage arrestors, cooling fans, a human-machine interface, and 24 power cells — field-replaceable modules that simplify maintenance. Control supply is 220 V AC, 3 kVA external; cooling fan supply is 380 V AC internal. Optional external supply for control at 220 V AC/DC and for cooling fan at 380 V AC. Analogue inputs: 4 software-configurable (0...20 mA / 4...20 mA, 24 V max, 250 Ohm). Analogue output: 1 software-configurable (0...20 mA / 4...20 mA DC, 250 Ohm). Discrete inputs: 6 (10 optional).

CE marked, compliant with EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3, EN/IEC 61800-4, and EN/IEC 61800-5-1. Electrical isolation between power and control circuits.

MPN
ATV1200A28001010