Schneider Electric ATV1200A3703333 — AC Drive (VFD) 480V

Schneider Electric ATV1200A3703333 AC Drive, 370 kVA, 309 kW

MPNATV1200A3703333
Active

Schneider Electric Altivar 1200 series, ATV1200A3703333 medium-voltage AC drive, 370 kVA apparent power, 309 kW motor power, 3.3 kV supply, 18-pulse rectifier, floor-standing enclosure.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A3703333 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A3703333 — Power & Output
ParameterValue
Motor power (kW)309 kW
Continuous output current65 A (standard overload) 52 A (high overload)
Max. transient current78 A for 60 s
Apparent power370 kVA

Input / Supply

ATV1200A3703333 — Input / Supply
ParameterValue
Rated supply voltage range3.3 kV +/- 10 %
Input line current65 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A3703333 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesClosed-loop control with encoder Vector control with sensor, optional Sensorless flux vector control Voltage/frequency ratio (V/f)
Synchronous motor control modesClosed-loop control with encoder Voltage/frequency ratio (V/f)

Protection & EMC

ATV1200A3703333 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A3703333 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP42 IP31 IP41
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A3703333 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A3703333 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A3703333 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

Physical footprint and enclosure integration

The ATV1200A3703333: Floor-standing enclosure with separate air flows — the standard-efficiency variant measures 2460 mm wide by 2520 mm high by 1400 mm deep; the high-efficiency variant adds width (2760 mm) and depth (1500 mm) to accommodate additional cooling capacity. The enclosure colour is grey RAL 7032. Forced-convection cooling moves 9900 m³/h (standard) or 13200 m³/h (high efficiency) through the cabinet, so the installation site must provide unobstructed airflow paths and clearance per the cabinet drawing.

Medium-voltage input and 18-pulse topology

Rated for a 2970…3630 V supply, the drive draws 65 A line current and delivers 370 kVA apparent power — enough for a 309 kW motor load on asynchronous or synchronous machines. The 18-pulse diode rectifier bridge reduces input current harmonics below IEEE 519 thresholds without an external filter, which simplifies upstream transformer sizing and avoids the cost of a separate harmonic filter cabinet. Output voltage tracks the supply voltage (≤ power supply voltage), so the motor sees the full line voltage minus internal drops — no step-up or step-down transformation inside the drive.

Overload capability and motor protection

Standard overload profile: 1.2× In for 60 s or 1.5× In for 3 s. High-overload profile: 1.5× In for 60 s or 1.85× In for 3 s. The choice between standard and high overload determines the continuous current rating of the power cells and affects the thermal budget of the enclosure. Ground-fault protection is built into the drive, and the dielectric strength between earth and power terminals is 10 kV AC — this covers the insulation coordination for a 3.3 kV system with overvoltage category II per EN/IEC 61800-5-1.

Auxiliary supplies and control wiring

The control electronics require an external 220 V AC supply rated at 3 kVA. The cooling fans draw from a separate 380 V AC supply — or optionally from 220 V AC/DC for the control and 380 V AC for the fans. These are not derived from the main DC bus, so the drive can be commissioned and the control powered up before the medium-voltage supply is applied. Four software-configurable analogue inputs (0…20 mA / 4…20 mA, 250 Ω impedance) and one analogue output (same range) handle speed reference and feedback. Six discrete inputs are standard, expandable to ten with an optional I/O board.

Standards, compliance, and lifecycle

CE marked. Designed to EN/IEC 60204-11, EN/IEC 60529, EN/IEC 61800-3 (EMC), EN/IEC 61800-4, and EN/IEC 61800-5-1. The integrated EMC filter covers conducted emissions for the first environment (restricted distribution) per the standard.

MPN
ATV1200A3703333