Skip to main content
Schneider Electric ATV1200A37803333 — AC Drive (VFD) 480V

Schneider ATV1200A37803333 AC Drive VFD, 3160 kW

MPNATV1200A37803333
Active

Schneider Electric Altivar 1200 series, ATV1200A37803333 medium-voltage AC drive, 3160 kW motor power, 2970-3630 V supply, 18-pulse diode rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A37803333 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A37803333 — Power & Output
ParameterValue
Motor power (kW)3160 kW
Continuous output current661 A (standard overload) 529 A (high overload)
Max. transient current794 A for 60 s
Apparent power3780 kVA

Input / Supply

ATV1200A37803333 — Input / Supply
ParameterValue
Rated supply voltage range3.3 kV +/- 10 %
Input line current720 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A37803333 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVoltage/frequency ratio (V/f) Vector control with sensor, optional Closed-loop control with encoder Sensorless flux vector control
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder

Protection & EMC

ATV1200A37803333 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A37803333 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP41 IP31 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A37803333 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A37803333 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A37803333 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

Medium-voltage drive for 3 MW motor loads

The Schneider Electric ATV1200A37803333 is an Altivar 1200 series medium-voltage AC drive rated for 3160 kW motor power with a supply voltage range of 2970 to 3630 V. This is a floor-standing cabinet assembly measuring 5870 mm wide by 2740 mm tall by 1700 mm deep — it occupies a dedicated substation room, not a panel. The 18-pulse diode rectifier bridge input topology inherently mitigates line harmonics, reducing the need for external filters. The drive handles both asynchronous and synchronous motors, with a speed range of 20 to 100% and 720 A line current at full load. Apparent power rating is 3780 kVA.

Overload profiles and duty cycle planning

Four distinct overload profiles are available: 1.2× rated current for 60 seconds (standard), 1.5× for 3 seconds (standard), 1.5× for 60 seconds (high overload), and 1.85× for 3 seconds (high overload). Match the profile to your application's peak torque demand — a crusher or centrifuge start may need the high-overload 60-second window. The prospective line short-circuit current rating is 31.5 kA for 150 ms, which sets the upstream protection coordination requirement. Ground fault protection is integrated into the drive. Dielectric strength between earth and power terminals is 10 kV AC, with electrical isolation between power and control circuits.

System architecture and cooling demands

The drive comprises 2 plinths, a phase-shifting transformer, 9 power cells, medium-voltage arrestors, cooling fans, and a human-machine interface. Forced convection cooling moves 60000 m³/h of air — the installation room must have corresponding ventilation or ducting. Noise level is 80 dB, so ear protection zones and acoustic treatment may be needed near the drive. Operating altitude is limited to 1000 m with derating of 0.6% per 100 m up to 2000 m. The control section requires an external 220 V AC supply at 3 kVA; the cooling fan runs on 380 V AC. An optional external supply for control at 220 V AC/DC is available, as is an optional external fan supply at 380 V AC.

Control interface and field wiring

The drive provides 4 software-configurable analogue inputs (0-20 mA / 4-20 mA, 24 V max, 250 Ohm impedance), 1 analogue output (same current ranges), and 6 discrete inputs expandable to 10. The I/O is suitable for basic speed reference, feedback, and start/stop commands. Power connection uses bar-type M10 screw terminals accepting 6 x 40 mm² cable per phase, with entry from the bottom or top. Output voltage is at or below the supply voltage. An integrated EMC filter is standard. Compliance standards include EN/IEC 61800-3 (EMC), EN/IEC 61800-4, EN/IEC 61800-5-1, EN/IEC 60204-11, and EN/IEC 60529. CE marking is applied.

Environmental limits for installation planning

Relative humidity range is 0 to 90% non-condensing, optionally 0 to 95%. Operating position must be vertical within ±10 degrees. Vibration resistance is 4.9 m/s² over 10 to 50 Hz. The enclosure colour is grey (RAL 7032). Assembly style is floor-standing with separate air flows for power and control sections.

Frequently asked questions

What compliance documentation does Schneider Electric provide for ATV1200A37803333?

The drive carries CE marking and complies with EN/IEC 61800-3 (EMC), EN/IEC 61800-4, EN/IEC 61800-5-1, EN/IEC 60204-11, and EN/IEC 60529. Dielectric strength is 10 kV AC between earth and power terminals, with electrical isolation between power and control circuits.

MPN