Skip to main content
Schneider Electric ATV1200A5306363 — AC Drive (VFD) 480V

Schneider Electric ATV1200A5306363 AC Drive, 376 kW

MPNATV1200A5306363
Active

Schneider Electric Altivar 1200 series, ATV1200A5306363 medium-voltage AC drive, 376 kW motor power, 2970-3630 V supply, 450 kVA, 36-pulse rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A5306363 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A5306363 — Power & Output
ParameterValue
Motor power (kW)376 kW
Continuous output current41 A (standard overload) 33 A (high overload)
Max. transient current49 A for 60 s
Apparent power450 kVA

Input / Supply

ATV1200A5306363 — Input / Supply
ParameterValue
Rated supply voltage range6.3 kV +/- 10 %
Input line current65 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A5306363 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVoltage/frequency ratio (V/f) Sensorless flux vector control Vector control with sensor, optional Closed-loop control with encoder
Synchronous motor control modesClosed-loop control with encoder Voltage/frequency ratio (V/f)

Protection & EMC

ATV1200A5306363 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A5306363 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP42 IP41
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A5306363 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A5306363 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A5306363 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

Medium-voltage drive for 3.3 kV class motors

The ATV1200A5306363 is an Altivar 1200 medium-voltage AC drive rated for 376 kW motor power with a supply voltage range of 2970 to 3630 V AC — a 3.3 kV class input that drives standard asynchronous and synchronous motors in the 400-500 hp band. Apparent power rating is 450 kVA, and the 36-pulse diode rectifier bridge draws 65 A line current, keeping input harmonics low enough to meet IEEE 519 without external filters in most installations.

36-pulse topology and overload capability

The 36-pulse input stage cancels the 5th, 7th, 11th, and 13th harmonics at the transformer secondary — a meaningful advantage on a mill or pump drive where upstream transformer heating from harmonic currents shortens service life. Overload profile is configurable: standard overload handles 1.2× rated current for 60 s or 1.5× for 3 s; high overload mode extends to 1.5× for 60 s and 1.85× for 3 s, matching the duty cycle of a crusher or centrifuge start. Prospective line short-circuit withstand is 31.5 kA for 150 ms — the drive's internal fault-limiting design coordinates with upstream MV switchgear without requiring additional current-limiting reactors.

Physical layout and cooling demands

Assembled in a floor-standing enclosure with separate air flows for the power cell section and control compartment — the standard-efficiency variant measures 3060 mm wide × 1400 mm deep × 2520 mm high; the high-efficiency variant is slightly larger at 3360 mm × 1500 mm × 2670 mm. Forced-convection cooling moves 13200 m³/h (standard) or 16500 m³/h (high efficiency); the acoustic noise level at full fan speed is 80 dB — plan for hearing protection zones around the drive cabinet. Electrical connection uses M10 screw-type bars accepting up to 6 × 40 mm² conductors per phase, with cable entry from the top or bottom of the enclosure.

Compliance and production status

CE marked and designed to EN/IEC 61800-3 (EMC), EN/IEC 61800-4 (thermal), EN/IEC 61800-5-1 (safety), EN/IEC 60204-11 (electrical equipment), and EN/IEC 60529 (enclosure protection). Pollution degree 2 per IEC 61800-5-1, overvoltage category II. Lifecycle stage is current production — the ATV1200 series remains an active Schneider Electric catalog line with no announced end-of-life or successor. Ground fault protection is integrated into the drive, and the dielectric strength between earth and power terminals is tested at 20 kV AC.

Frequently asked questions

What motor power and voltage does the ATV1200A5306363 support?

It is rated for 376 kW motor power on a 2970 to 3630 V AC supply, with 450 kVA apparent power. It drives both asynchronous and synchronous motors.

Where can I buy the ATV1200A5306363 and check availability?

This drive is sourced through independent distribution channels.

MPN
ATV1200A5306363