Skip to main content
Schneider Electric ATV1200A66606363 — AC Drive (VFD) 480V

Schneider Electric ATV1200A66606363 AC Drive, 5016 kW

MPNATV1200A66606363
Active

Schneider Electric Altivar 1200 series, ATV1200A66606363 AC drive, 5016 kW motor power, 36-pulse diode rectifier input, 2970-3630 V supply, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A66606363 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A66606363 — Power & Output
ParameterValue
Motor power (kW)5016 kW
Continuous output current550 A (standard overload) 440 A (high overload)
Max. transient current660 A for 60 s
Apparent power6000 kVA

Input / Supply

ATV1200A66606363 — Input / Supply
ParameterValue
Rated supply voltage range6.3 kV +/- 10 %
Input line current550 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A66606363 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesClosed-loop control with encoder Sensorless flux vector control Voltage/frequency ratio (V/f) Vector control with sensor, optional
Synchronous motor control modesClosed-loop control with encoder Voltage/frequency ratio (V/f)

Protection & EMC

ATV1200A66606363 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A66606363 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP41 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A66606363 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A66606363 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A66606363 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

What this drive is and what it powers

The ATV1200A66606363 is a Schneider Electric Altivar 1200 medium-voltage AC drive rated for 5016 kW motor power, designed for asynchronous motors in heavy industrial applications. It sits in a floor-standing enclosure with separate air flows for the power section and control electronics. The 36-pulse diode rectifier bridge on the input side means this drive draws line current with low harmonic distortion — 550 A line current at 6000 kVA apparent power — which keeps the upstream transformer and switchgear from overheating on harmonic-rich loads.

Physical size and site planning

This is a large unit: 3040 mm tall, 8570 mm wide, 1800 mm deep. The volume of cooling air required is 90,000 m³/h, so the installation room needs substantial ventilation or ducted exhaust. Forced-convection cooling with separate air flows means the power cell heat is rejected directly rather than warming the control cabinet.

Overload capability and protection

Standard overload rating: 1.2× rated current for 60 seconds, or 1.5× for 3 seconds. High overload profile: 1.5× for 60 seconds, 1.85× for 3 seconds. This matters when the driven load has a heavy breakaway torque or a short-duration peak — a crusher or a centrifuge, for example — because the drive holds torque through the transient without tripping. Ground fault protection is built into the drive, and the prospective short-circuit current withstand is 31.5 kA for 150 ms. Dielectric strength between earth and power terminals is 20 kV AC. The pollution degree is 2 per EN/IEC 61800-5-1, which covers the normal industrial environment with non-conductive dust.

Control supply and I/O

The control electronics need an external 220 V AC supply rated at 3 kVA. There is also an optional external 220 V AC/DC supply. The cooling fans run on a separate 380 V AC supply — this separation means you can keep the control alive while the main power is off, which helps during commissioning and fault-finding. Four software-configurable analogue inputs (0-20 mA / 4-20 mA, 250 Ω impedance) and one analogue output (same range). Six discrete inputs standard, expandable to ten. The I/O is electrically isolated from the power stage, so field wiring faults on the control side won't propagate into the drive's power section.

CE marked, with integrated EMC filter. Standards compliance includes EN/IEC 60204-11 (electrical equipment of machines), EN/IEC 60529 (IP enclosure), EN/IEC 61800-3 (EMC for drives), EN/IEC 61800-4 (drive performance), and EN/IEC 61800-5-1 (electrical safety). Overvoltage category II per the same safety standard.

Frequently asked questions

What supply voltage does the ATV1200A66606363 need?

The supply voltage limits are 2970 to 3630 V AC. The input is a 36-pulse diode rectifier bridge drawing 550 A line current at 6000 kVA apparent power.

What overload ratings does this drive support?

Standard overload: 1.2× rated current for 60 seconds or 1.5× for 3 seconds. High overload: 1.5× for 60 seconds or 1.85× for 3 seconds. This gives flexibility for applications with high breakaway torque or short-duration peak loads.

MPN
ATV1200A66606363