Skip to main content
Schneider Electric ATV1200A9406060 — AC Drive (VFD) 480V

Schneider ATV1200A9406060 AC Drive, 940 kVA, 786 kW, 3 kV

MPNATV1200A9406060
Active

Schneider Electric Altivar 1200 ATV1200A9406060 medium-voltage AC drive, 940 kVA, 786 kW motor power, 2970-3630 V supply, 30-pulse rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV1200A9406060 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV1200
Product range / familyAltivar 1200

Power & Output

ATV1200A9406060 — Power & Output
ParameterValue
Motor power (kW)786 kW
Continuous output current90 A (standard overload) 72 A (high overload)
Max. transient current108 A for 60 s
Apparent power940 kVA

Input / Supply

ATV1200A9406060 — Input / Supply
ParameterValue
Rated supply voltage range6 kV +/- 10 %
Input line current100 A
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for control at 220 V AC, 3 kVA Internal supply for cooling fan at 380 V AC External supply for control at 220 V AC/DC (optional) External supply for cooling fan at 380 V AC (optional)

Control & Performance

ATV1200A9406060 — Control & Performance
ParameterValue
Output frequency range0.5...120 Hz voltage/frequency ratio (V/f) 0.5...70 Hz vector control with/without speed feedback
Asynchronous motor control modesVoltage/frequency ratio (V/f) Sensorless flux vector control Vector control with sensor, optional Closed-loop control with encoder
Synchronous motor control modesVoltage/frequency ratio (V/f) Closed-loop control with encoder

Protection & EMC

ATV1200A9406060 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated
Protection functionsGround fault protection: drive
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV1200A9406060 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 IP41 IP42
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure with separate air flows

Environmental

ATV1200A9406060 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C (with current derating of 2 % per °C)
Operating altitude1000...2000 m with current derating 0.6 % per 100 m
Relative humidity0...90 % 0...95 % optional
Storage / transport temperature-10...60 °C
Pollution degree2 conforming to EN/IEC 61800-5-1
Vibration resistance4.9 m/s² (f= 10...50 Hz)

Approvals

ATV1200A9406060 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceEN/IEC 60204-11 EN/IEC 60529 EN/IEC 61800-3 EN/IEC 61800-4 EN/IEC 61800-5-1

Communication

ATV1200A9406060 — Communication
ParameterValue
Communication protocolsHuman machine interface: Modbus with 2-wire RS485(1) - SUB-D 9 Human machine interface: Modbus TCP with (1) - RJ45 Human machine interface: EtherNet/IP with (1) - RJ45 Human machine interface: Profibus with (1) - SUB-D 9 Human machine interface: DeviceNet with (1) - SUB-D 9

Product details

940 kVA at 3 kV — what the rating means for the load

The ATV1200A9406060 is rated for 940 kVA apparent power and 786 kW motor power, fed from a 2970-3630 V supply — this is a medium-voltage drive sized for large induction or synchronous motors in the 800 kW class. The 30-pulse diode rectifier bridge at the input keeps line-side harmonics low enough to skip a separate filter in most utility grids — the integrated EMC filter handles the drive-side emissions. Overload capability is 1.2× rated current for 60 seconds standard duty, or 1.5× for 3 seconds; high-overload profile pushes to 1.5× for 60 seconds and 1.85× for 3 seconds — match this to your load cycle before committing the BOM line.

Floor-standing enclosure — physical integration constraints

This drive ships in a floor-standing enclosure with separate air flows — the standard-efficiency variant measures 2860 mm wide × 2590 mm high × 1400 mm deep; the high-efficiency variant is wider at 3460 mm and taller at 2740 mm, with depth increasing to 1500 mm (-). Forced-convection cooling moves 16600 m³/h on the standard build and 23200 m³/h on the high-efficiency build — the room's ventilation must handle that airflow without recirculating hot exhaust into the intake. Operating altitude derates current 0.6 % per 100 m above 1000 m; the drive must sit vertical within ±10°.

No pin-compatible alternative exists in the Altivar 1200 family — the footprint and voltage class are unique to this order code.

MPN
ATV1200A9406060