Skip to main content
Schneider Electric ATV212HD55N4 — AC Drive (VFD) 480V

Schneider Electric ATV212HD55N4 AC Drive, 55 kW, 480 V

MPNATV212HD55N4
Obsolete

Schneider Electric Altivar 212 ATV212HD55N4 AC drive, 55 kW, 3-phase 480 V, 102.7 A line current at 380 V, integrated Class C2 EMC filter, IP20, with heat sink.

$3,273.76 – $8,556.73Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV212HD55N4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV212
Product range / familyAltivar 212
ATV212HD55N4 — Power & Output
ParameterValue
Motor power (kW)55 kW
Continuous output current116 A 380 V 116 A 460 V
Max. transient current127.6 A 60 s
Apparent power76.3 kVA 380 V
ATV212HD55N4 — Input / Supply
ParameterValue
Rated supply voltage range380...480 V - 15...10 %
Input line current102.7 A 380 V 89 A 480 V
ATV212HD55N4 — Control & Performance
ParameterValue
Output frequency range0.5...200 Hz
Asynchronous motor control modesVoltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points
ATV212HD55N4 — Protection & EMC
ParameterValue
Integrated EMC filter classClass C2 EMC filter integrated
Protection functionsOverheating protection drive Thermal power stage drive Short-circuit between motor phases drive Input phase breaks drive Overcurrent between output phases and earth drive Overvoltages on the DC bus drive Break on the control circuit drive Against exceeding limit speed drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Against input phase loss drive Thermal protection motor Motor phase break motor With PTC probes motor
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Prospective short-circuit current (Isc)22 kA
ATV212HD55N4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP21
Acoustic noise level63.7 dB 86/188/EEC
Assembly / installation styleWith heat sink
ATV212HD55N4 — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) (without derating) 104...122 °F (40...50 °C) (with derating factor)
Operating altitude3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating
Relative humidity5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3
Storage / transport temperature-13...158 °F (-25...70 °C)
Pollution degree3 IEC 61800-5-1
Vibration resistance1.5 mm (f= 3...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8
ATV212HD55N4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C3 IEC 61800-5-1 IEC 61800-3 IEC 61800-3 environments 2 category C1 IEC 61800-3 IEC 61800-3 environments 1 category C2 EN 55011 class A group 1 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-3 environments 2 category C2 UL Type 1 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-5-1 EN 61800-3 category C3 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 category C2 IEC 61800-3 environments 2 category C1
ATV212HD55N4 — Communication
ParameterValue
Communication protocolsMETASYS N2 BACnet LonWorks APOGEE FLN Modbus

Product details

55 kW VFD with integrated C2 EMC filter

The Schneider Electric ATV212HD55N4 is a 55 kW variable speed drive from the Altivar 212 range, designed for 3-phase 480 V supply. It draws 102.7 A line current at 380 V and 89 A at 480 V, so at 480 V the full 55 kW motor power is available without oversizing the input wiring. An integrated Class C2 EMC filter is fitted as standard, which means the drive meets conducted emission limits for industrial environments without an external filter box — saves panel space and one installation step. The protection set covers the common failure modes: overcurrent between output phases and earth, DC bus overvoltage, input phase loss, motor thermal protection via PTC probes, and short-circuit between motor phases. The drive also monitors line supply undervoltage and overvoltage, so nuisance trips from a sagging grid are caught before the motor stalls.

Lifecycle and compliance

Compliance covers IEC 61800-5-1 (safety), IEC 61800-3 (EMC environments 1 and 2, categories C1 through C3), EN 55011 Class A Group 1, and UL Type 1. The CE marking and the range of IEC categories mean the drive can be installed in most industrial and light-commercial settings without additional filtering or shielding for the drive itself.

Sourcing and availability

This drive is quoted to order against the BOM quantity. Availability and current pricing are confirmed at RFQ — no stock-holding claim, but the mature lifecycle means production quantities are generally accessible through authorized distribution channels.

MPN
ATV212HD55N4