ATV212WD11N4CZH28
Schneider Electric ATV212WD11N4CZH28
MPNATV212WD11N4CZH28
Obsolete
variable speed drive ATV212 - IP54 - 11 kW 3x380 480 V
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jun 2026
Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Device short name | ATV212 |
| Product range / family | Altivar 212 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 11 kW |
| Continuous output current | 22.5 A at 380 V 22.5 A at 460 V |
| Max. transient current | 24.8 A for 60 s |
| Apparent power | 17.1 kVA at 380 V |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 380...480 V - 15...10 % |
| Input line current | 21.1 A at 380 V 16.7 A at 480 V |
| Network number of phases | 3 phases |
Control & Performance
| Parameter | Value |
|---|---|
| Output frequency range | 0.5...200 Hz |
| Asynchronous motor control modes | Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 2 points |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Class C1 EMC filter integrated |
| Protection functions | Overheating protection: drive Thermal power stage: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply overvoltage and undervoltage: drive Line supply undervoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor With PTC probes: motor |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Prospective short-circuit current (Isc) | 22 kA |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP54 conforming to EN/IEC 61800-5-1 IP54 conforming to EN/IEC 60529 |
| Acoustic noise level | 57.4 dB conforming to 86/188/EEC |
| Assembly / installation style | With heat sink |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -10...40 °C (without derating) 40...50 °C (with derating factor) |
| Operating altitude | 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m <= 1000 m without derating |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 5...95 % without dripping water conforming to IEC 60068-2-3 |
| Storage / transport temperature | -25...70 °C |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
| Vibration resistance | 1.5 mm (f= 3...13 Hz) conforming to EN/IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to EN/IEC 60068-2-8 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | EN 61800-3 environments 1 category C1 IEC 61800-3 category C1 EN 61800-5-1 IEC 61800-5-1 EN 61800-3 environments 2 category C1 IEC 61800-3 EN 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 1 category C3 EN 61800-3 category C1 IEC 61800-3 environments 2 category C2 EN 55011 group 1 class B EN 61800-3 EN 61800-3 environments 2 category C3 EN 61800-3 environments 2 category C2 EN 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C3 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | METASYS N2 Modbus APOGEE FLN LonWorks BACnet |
MPN