Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Product range / family | Altivar 32 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 5.5 kW at 380...480 V |
| Max. transient current | 21.5 A for 60 s 5.5 kW / 7.5 hp |
| Apparent power | 17.9 kVA at 500 V 3 phases 5.5 kW / 7.5 hp |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 380...500 V - 15...10 % |
| Input line current | 14.5 A for 500 V 3 phases 5.5 kW / 7.5 hp 20.7 A for 380 V 3 phases 5.5 kW / 7.5 hp |
| Network number of phases | 3 phases |
| Internal/auxiliary supplies | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
Control & Performance
| Parameter | Value |
|---|---|
| Asynchronous motor control modes | Voltage/frequency ratio, 2 points Flux vector control without sensor - Energy Saving, NoLoad law Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f |
| Synchronous motor control modes | Vector control without sensor |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Class C2 EMC filter integrated |
| Protection functions | Input phase breaks: drive Overcurrent between output phases and earth: drive Overheating protection: drive Short-circuit between motor phases: drive Thermal protection: drive |
| EMC immunity tests | 1.2/50 µs - 8/20 µs surge immunity test, level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test, level 3 conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test, level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test, level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test, level 3 conforming to IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
| Prospective short-circuit current (Isc) | 22 kA for 3 phases |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to EN/IEC 61800-5-1 |
| Acoustic noise level | 43 dB conforming to 86/188/EEC |
| Assembly / installation style | With heat sink |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -10...50 °C without derating 50...60 °C with derating factor |
| Operating altitude | 1000...3000 m with current derating 1 % per 100 m |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 5...95 % without dripping water conforming to IEC 60068-2-3 |
| Storage / transport temperature | -25...70 °C |
| Pollution degree | 2 conforming to EN/IEC 61800-5-1 |
| Vibration resistance | 1 gn (f = 13...200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm peak to peak (f = 3...13 Hz) conforming to EN/IEC 60068-2-6 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | EN 61800-3 environments 2 category C2 EN/IEC 61800-5-1 EN 61800-3 environments 1 category C2 EN 55011 class A group 1 EN/IEC 61800-3 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | CANopen Modbus |
MPN