Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Medium voltage variable speed drive |
| Device short name | ATV6000 |
| Product range / family | Altivar Process ATV6000 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 800 kW for normal duty 750 kW for heavy duty |
| Continuous output current | 52 A heavy duty 55.2 A normal duty |
| Max. transient current | 97.5 A during 3 s (heavy duty) 82.8 A during 3 s (normal duty) |
| Apparent power | 1000 kVA |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 10 kV +/- 10 % |
| Input line current | 54 A heavy duty 57.8 A normal duty |
| Network number of phases | 3 phases |
| Internal/auxiliary supplies | Internal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA |
Control & Performance
| Parameter | Value |
|---|---|
| Output frequency range | 0.1...120 Hz |
| Asynchronous motor control modes | Closed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop |
| Synchronous motor control modes | Permanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power |
| Protection functions | Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive |
| EMC immunity tests | Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Prospective short-circuit current (Isc) | 31.5 kA for 150 ms |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP31 conforming to IEC 60529 |
| Acoustic noise level | 80 dB |
| Cooling method | Forced convection |
| Assembly / installation style | In floor-standing enclosure |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | 0...40 °C 40...50 °C with derating factor -25...70 °C during transport |
| Operating altitude | 1000...2000 m with derating factor |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 |
| Storage / transport temperature | 0...50 °C |
| Pollution degree | 2 conforming to IEC 61800-5-1 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | EAC CE |
| Standards compliance | IEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | Ethernet IP/Modbus TCP |
MPN