Skip to main content
Schneider Electric ATV6000C179A6666NA3 — AC Drive (VFD) 480V

ATV6000C179A6666NA3 Altivar Process ATV6000, 1140 kW HD, 179

MPNATV6000C179A6666NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000C179A6666NA3, medium-voltage drive, 1140 kW heavy duty / 1430 kW normal duty, 1790 kVA, 36-pulse diode rectifier, THDI <3%.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000C179A6666NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000C179A6666NA3 — Power & Output
ParameterValue
Motor power (kW)1140 kW for heavy duty 1430 kW for normal duty
Continuous output current120 A heavy duty 150 A normal duty
Max. transient current225 A during 3 s (heavy duty) 225 A during 3 s (normal duty)
Apparent power1790 kVA

Input / Supply

ATV6000C179A6666NA3 — Input / Supply
ParameterValue
Rated supply voltage range6.6 kV +/- 10 %
Input line current125 A heavy duty 157 A normal duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 12 kVA

Control & Performance

ATV6000C179A6666NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000C179A6666NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000C179A6666NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level83 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000C179A6666NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000C179A6666NA3 — Approvals
ParameterValue
Certifications & markingEAC CE
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000C179A6666NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The Schneider Electric ATV6000C179A6666NA3 is a medium-voltage Altivar Process ATV6000 drive rated for 1140 kW heavy duty and 1430 kW normal duty, with an apparent power of 1790 kVA. It uses a 36-pulse diode rectifier front end to keep input current THDI below 3 % per IEEE 519-1992, which means it meets harmonic limits without an external filter for most industrial grids. The drive is in current lifecycle stage, so it remains a standard catalog item for new projects and expansions.

Motor power is 1140 kW for heavy-duty applications (constant torque, conveyors, extruders) and 1430 kW for normal duty (variable torque, pumps, fans). The 36-pulse rectifier delivers a power factor of 0.96, reducing the need for power-factor correction capacitors. Output voltage is limited to the supply voltage, so the drive does not boost voltage above the line — factor that into motor nameplate matching. Power losses are 49.6 kW at heavy duty and 62.2 kW at normal duty, which drives enclosure ventilation requirements. The forced-convection cooling system and integrated EMC filter (C3 for control circuit, C4 for power circuit) are built into the floor-standing enclosure. Noise level is 83 dB, so ear protection is needed near the cabinet.

Integration and fieldbus options

Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT. Slot B takes encoder interface modules (5/12 V digital, analog, resolver, or HTL). Both slots can also host digital/analog I/O extension or output relay extension modules. The 10-inch LCD touch screen provides multi-language HMI for local commissioning.

Frequently asked questions

What are the motor power ratings for this drive?

It is rated for 1140 kW in heavy duty and 1430 kW in normal duty, with an apparent power of 1790 kVA.

What harmonic performance does the 36-pulse rectifier provide?

Input current THDI is below 3 % conforming to IEEE 519-1992, eliminating the need for external harmonic filters in most installations.

What fieldbus options are available?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT modules. Slot B takes encoder interface modules.

What compliance documentation does this drive carry?

Markings include EAC and CE. Standards listed are IEC 61800-3, EN/IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076.

MPN
ATV6000C179A6666NA3