The Schneider ATV6000C288A6666NA3 is a medium-voltage drive from the Altivar Process ATV6000 family, rated for 2300 kW normal duty and 2140 kW heavy duty motor loads. It delivers 2880 kVA apparent power and draws 252 A normal duty line current or 234 A heavy duty. The 30-pulse diode rectifier bridge keeps input THDI below 3% per IEEE 519-1992, so you can skip a separate harmonic filter on most utility feeds.
Floor-standing enclosure, 4660 mm wide × 1600 mm deep × 2751 mm tall. Cable entry is bottom-only — plan your gland plate and tray routing accordingly. Forced convection cooling; the fan supply is a separate 400 V AC ±10% at 17 kVA, so the cooling circuit is independent of the main drive power. Noise level is 83 dB — factor that into any nearby operator station or enclosure placement. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT communication modules. Slot B takes encoder interfaces (5/12 V digital, analog, resolver, HTL). Both slots also accept digital/analog I/O extension or output relay extension modules. The control block has two RJ45 for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial.