Skip to main content
Schneider Electric ATV6000C325A1010NA3 — AC Drive (VFD) 480V

Schneider ATV6000C325A1010NA3 Medium Voltage Drive, 3250 kVA

MPNATV6000C325A1010NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000C325A1010NA3, medium voltage drive, 3250 kVA, 2600 kW normal duty motor power, 48-pulse diode rectifier, IGBT inverter cells, floor-standing enclosure.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV6000C325A1010NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000
ATV6000C325A1010NA3 — Power & Output
ParameterValue
Motor power (kW)2600 kW for normal duty 2310 kW for heavy duty
Continuous output current160 A heavy duty 180 A normal duty
Max. transient current300 A during 3 s (heavy duty) 269 A during 3 s (normal duty)
Apparent power3250 kVA
ATV6000C325A1010NA3 — Input / Supply
ParameterValue
Rated supply voltage range10 kV +/- 10 %
Input line current167 A heavy duty 188 A normal duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA
ATV6000C325A1010NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor
ATV6000C325A1010NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms
ATV6000C325A1010NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure
ATV6000C325A1010NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1
ATV6000C325A1010NA3 — Approvals
ParameterValue
Certifications & markingEAC CE
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076
ATV6000C325A1010NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The ATV6000C325A1010NA3: The drive draws 167 A line current in heavy duty and 188 A in normal duty, with a power factor of 0.96. Power losses are 100.4 kW heavy duty and 113 kW normal duty — that heat has to be managed by the forced-convection cooling system, so the installation room needs adequate ventilation or a dedicated cooling circuit. The 10-inch LCD touch screen provides local monitoring and parameter access in multiple languages.

Where this class of drive is used

Medium voltage drives like this one are used to control large induction, synchronous, or permanent magnet motors in applications such as pumps, fans, compressors, conveyors, and mills in industries like mining, oil and gas, water treatment, and cement. The 48-pulse rectifier and integrated EMC filter (C3 control, C4 power) suit installations where grid harmonic compliance is critical.

Frequently asked questions

What is the motor power rating for this drive?

It delivers 2600 kW in normal duty and 2310 kW in heavy duty.

What are the physical dimensions of the ATV6000C325A1010NA3?

The floor-standing enclosure measures 6160 mm wide, 2751 mm high, and 1700 mm deep.

What compliance documentation is available for this drive?

The drive carries EAC and CE markings, and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076 standards.

MPN