Skip to main content
Schneider Electric ATV6000C328A3333NA3

Schneider ATV6000C328A3333NA3 VFD, 2620 kW, 3280 kVA, 480V

MPN ATV6000C328A3333NA3
Active

Schneider Electric Altivar Process ATV6000 AC Drive, ATV6000C328A3333NA3, 2620 kW normal duty / 2100 kW heavy duty, 3280 kVA, 480 V class, 18-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000C328A3333NA3 specifications
ParameterValue
Input type18 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 (on the control block) for Ethernet IP/Modbus TCP 1 RJ45 (on the control block) for Modbus serial
Current574 A normal duty 458 A heavy duty
Frequency50 Hz +/- 5 %
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1
Depth1700 mm
Width5760 mm
Height2791 mm
Operating temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport

Product details

Power stage and motor ratings

The ATV6000C328A3333NA3: Rated 2620 kW for normal duty and 2100 kW for heavy duty, with an apparent power of 3280 kVA. The line current draw is 574 A at normal duty, 458 A at heavy duty — these numbers govern the incoming cable and transformer sizing, not the motor FLA alone. The 18-pulse diode rectifier input keeps total harmonic current distortion below 3 % per IEEE 519-1992, which means you can often skip an external harmonic filter on a dedicated transformer. Power factor is 0.96.

Physical footprint and enclosure

This is a floor-standing enclosure, not a wall-mount drive. Dimensions: 5760 mm wide, 1700 mm deep, 2791 mm high. Plan for a dedicated electrical room bay with front and rear access for cable entry from the bottom and forced-convection cooling airflow. Sound pressure level is 85 dB — hearing protection zones apply around the drive during operation.

Controls, communications, and I/O

The standard HMI is a 10-inch LCD colour touchscreen with multi-language support. Communication slots accept Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT on Slot A; encoder feedback modules (digital, analog, resolver, HTL) on Slot B. Built-in Ethernet IP/Modbus TCP on two RJ45 ports plus one dedicated Modbus serial RJ45. The 8 digital inputs include two programmable as pulse inputs up to 30 kHz; analogue inputs are configurable 0–10 V or 0–20 mA. Three configurable relay outputs (one NO/NC fault relay, two NO sequence relays) plus configurable analogue outputs (0–10 V / 0–20 mA).

Protection suite and compliance

The drive monitors line overvoltage, undervoltage, phase loss, DC bus overvoltage, transformer thermal overload, cabinet overtemperature, overcurrent, overload, short-circuit, and motor earth fault. Each IGBT power cell has its own thermal protection. Marked EAC and CE. Designed to IEC 61800-3 (EMC), IEC 61800-4, IEC 61800-5-1 (safety), and IEC 60529 (enclosure). Pollution degree 2 per IEC 61800-5-1. Integrated EMC filter meets category C3 on the control side and C4 on the power side.

MPN
ATV6000C328A3333NA3