Skip to main content
Schneider Electric ATV6000C375A1111NA3 — AC Drive (VFD) 480V

Schneider ATV6000C375A1111NA3 ATV6000, 3000 kW MV Drive

MPNATV6000C375A1111NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000C375A1111NA3, medium voltage drive, 3000 kW normal duty, 3750 kVA, 54-pulse diode rectifier, IGBT multilevel PWM.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV6000C375A1111NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000
ATV6000C375A1111NA3 — Power & Output
ParameterValue
Motor power (kW)3000 kW for normal duty 2540 kW for heavy duty
Continuous output current160 A heavy duty 188 A normal duty
Max. transient current300 A during 3 s (heavy duty) 282 A during 3 s (normal duty)
Apparent power3750 kVA
ATV6000C375A1111NA3 — Input / Supply
ParameterValue
Rated supply voltage range11 kV +/- 10 %
Input line current166 A heavy duty 197 A normal duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 8 kVA
ATV6000C375A1111NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor
ATV6000C375A1111NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms
ATV6000C375A1111NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level83 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure
ATV6000C375A1111NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1
ATV6000C375A1111NA3 — Approvals
ParameterValue
Certifications & markingCE EAC
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076
ATV6000C375A1111NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The Schneider Electric ATV6000C375A1111NA3 is a medium voltage drive from the Altivar Process ATV6000 range, rated for 3000 kW normal duty and 2540 kW heavy duty, with an apparent power of 3750 kVA. It uses a 54-pulse diode rectifier bridge on the input and IGBT inverter cells with multilevel PWM on the output, keeping input current THDI below 3% per IEEE 519-1992.

The 3750 kVA apparent power tells you the transformer and cable sizing upstream need to handle that full-load kVA, not just the motor kW. Line current is 197 A normal duty, 166 A heavy duty, so the incoming feeder and fusing should be specced for at least the normal-duty figure.

Installation and compliance

Cable entry is at the bottom. The drive includes an integrated EMC filter: category C3 on the control side, C4 on the power side. Standards compliance covers IEC 61800-3 (EMC), IEC 61800-5-1 (safety), and IEEE 519-1992 (harmonic distortion). Marked CE and EAC. The 10-inch LCD touch screen is the local HMI; the control block has two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial. Option card slots A and B accept communication modules (PROFIBUS, PROFINET, EtherCAT, DeviceNet, CANopen) and encoder interfaces (digital 5/12 V, analog, resolver, HTL).

Frequently asked questions

What are the key ratings for this drive?

Motor power is 3000 kW normal duty, 2540 kW heavy duty. Apparent power is 3750 kVA. Line current is 197 A normal duty, 166 A heavy duty. Input THDI is below 3%.

What compliance documentation does the ATV6000C375A1111NA3 carry?

It is marked CE and EAC, and conforms to IEC 61800-3, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076.

What are the physical dimensions of this drive?

Height 2751 mm, depth 1700 mm, width 6660 mm.

MPN
ATV6000C375A1111NA3