Schneider Electric ATV6000C382A6666ND — AC Drive (VFD) 480V

Schneider ATV6000C382A6666ND AC Drive, 3050 kW, 480V

MPNATV6000C382A6666ND
Active

Schneider Electric Altivar Process ATV6000 AC drive, ATV6000C382A6666ND, 3050 kW normal duty, 3-phase 480V, 30-pulse diode rectifier, IGBT multilevel PWM output, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000C382A6666ND — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000C382A6666ND — Power & Output
ParameterValue
Motor power (kW)3050 kW normal duty 2930 kW heavy duty
Continuous output current320 A normal duty 307 A heavy duty
Max. transient current480 A 3 s normal duty) 576 A 3 s heavy duty)
Apparent power3820 kVA

Input / Supply

ATV6000C382A6666ND — Input / Supply
ParameterValue
Rated supply voltage range6.6 kV +/- 10 %
Input line current334 A normal duty 320 A heavy duty
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 8 kVA

Control & Performance

ATV6000C382A6666ND — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000C382A6666ND — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated IEC 61800-3 category C3 control Integrated IEC 61800-3 category C4 Power
Protection functionsLine supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overvoltages on the DC bus drive Thermal overload for transformer drive Cabinet overheating drive Overcurrent drive Overload drive Short-circuit protection drive IGBT for each cell drive Thermal protection motor Motor phase break motor Motor earth fault motor Break on the control circuit drive Fan monitoring drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA 150 ms

Mechanical & Cooling

ATV6000C382A6666ND — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level83 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000C382A6666ND — Environmental
ParameterValue
Operating ambient temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport
Operating altitude3280.84...6561.68 ft (1000...2000 m) with derating factor
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature32...122 °F (0...50 °C)
Pollution degree2 IEC 61800-5-1

Approvals

ATV6000C382A6666ND — Approvals
ParameterValue
Certifications & markingCULus CE UKCA
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 UL 347A

Communication

ATV6000C382A6666ND — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The ATV6000C382A6666ND is a Schneider Electric Altivar Process ATV6000 AC drive rated for 3050 kW normal duty and 2930 kW heavy duty, with a 30-pulse diode rectifier input and IGBT multilevel PWM output. The 30-pulse topology keeps input current THDI below 3% per IEEE 519-1992, so it meets harmonic limits without external filters in most installations. Line current is 334 A normal duty, 320 A heavy duty, and apparent power is 3820 kVA at a power factor of 96.

Floor-standing enclosure and control supply

The drive ships in a floor-standing enclosure (66.9 in deep, 234.6 in wide, 108.3 in high) with bottom cable entry. It includes the enclosure, cooling fans, power cells, medium-voltage arrestors, phase-shifting transformer, HMI (10-inch LCD touchscreen), and plinth. The control circuit accepts 100–240 V AC 47–63 Hz or 120–370 V DC; the cooling fan runs on 400 V AC. Forced convection cooling keeps the IGBT cells within their thermal budget. Digital inputs DI1–DI8 are programmable at 24 V DC, with DI7 and DI8 configurable as pulse inputs up to 30 kHz. Two RJ45 ports on the control block handle Ethernet IP/Modbus TCP and Modbus serial. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT communication modules; Slot B accepts encoder interface modules (digital 5/12 V, analog, resolver, HTL) or I/O extension modules.

Protection coverage and motor compatibility

Protection extends to line supply overvoltage, undervoltage, phase loss, DC bus overvoltage, thermal overload for the transformer, cabinet overheating, overcurrent, overload, short-circuit protection, IGBT per-cell protection, motor thermal protection, motor phase break, motor earth fault, control circuit break, and fan monitoring. The drive is designed for permanent-magnet, synchronous, and asynchronous motors. Operating altitude is 1000–2000 m with derating; relative humidity 5–95% without condensation per IEC 60068-2-3. Pollution degree 2 per IEC 61800-5-1. Noise level is 83 dB.

Frequently asked questions

What compliance documentation does Schneider Electric provide for ATV6000C382A6666ND?

The drive carries CULus, CE, and UKCA marking and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.