Skip to main content
Schneider Electric ATV6000C585A6666ND

Schneider ATV6000C585A6666ND Altivar Process Drive, 4680 kW

MPN ATV6000C585A6666ND
Active

Schneider Electric Altivar Process ATV6000, ATV6000C585A6666ND, 3-phase, 4680 kW normal duty / 3740 kW heavy duty, 36-pulse diode rectifier, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000C585A6666ND specifications
ParameterValue
Input type36 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial
Current512 A normal duty 406 A heavy duty
Frequency50 Hz +/- 5 %
Phases3-phase
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature32...122 °F (0...50 °C)
Pollution degreePollution degree 2
Depth70.9 in (1800.0 mm)
Width270.08 in (6860.0 mm)
Height124.06 in (3151.0 mm)
Operating temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport

Product details

The ATV6000C585A6666ND is a Schneider Electric Altivar Process ATV6000 medium-voltage drive in a floor-standing enclosure, built around a 36-pulse diode rectifier bridge and IGBT inverter cells with multilevel PWM output. Rated for 4680 kW normal duty and 3740 kW heavy duty motor power, with corresponding line currents of 512 A and 406 A. The drive delivers an apparent power of 5850 kVA and a power factor of 96, with total harmonic current distortion (THDI) below 3% per IEEE 519-1992.

The heavy-duty current rating (406 A) is the figure to size cables and protection for continuous motor load; the normal-duty rating (512 A) applies when the drive is not expected to deliver full rated current continuously, such as in variable-torque fan/pump applications. Power losses are 177.2 kW at normal duty and 141.6 kW at heavy duty — that heat must be rejected by the forced-convection cooling system, and the enclosure's ventilation path needs clearance on both sides.

Compliance documentation includes CULus, CE, and UKCA markings, and the drive is designed to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.

Physical configuration

The enclosure measures 124.06 in (3151 mm) high, 270.08 in (6860 mm) wide, and 70.9 in (1800 mm) deep — a substantial footprint that requires a dedicated equipment room or pad, not a standard panel. Cable entry is at the bottom, and the drive ships with the phase-shifting transformer, plinth, cooling fans, power cells, HMI, and medium-voltage arrestors included.

MPN
ATV6000C585A6666ND