Skip to main content
Schneider Electric ATV6000C585A6666ND — AC Drive (VFD) 480V

Schneider ATV6000C585A6666ND Altivar Process Drive, 4680 kW

MPNATV6000C585A6666ND
Active

Schneider Electric Altivar Process ATV6000, ATV6000C585A6666ND, 3-phase, 4680 kW normal duty / 3740 kW heavy duty, 36-pulse diode rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000C585A6666ND — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000C585A6666ND — Power & Output
ParameterValue
Motor power (kW)3740 kW heavy duty 4680 kW normal duty
Continuous output current490 A normal duty 392 A heavy duty
Max. transient current735 A 3 s normal duty) 735 A 3 s heavy duty)
Apparent power5850 kVA

Input / Supply

ATV6000C585A6666ND — Input / Supply
ParameterValue
Rated supply voltage range6.6 kV +/- 10 %
Input line current512 A normal duty 406 A heavy duty
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 31 kVA

Control & Performance

ATV6000C585A6666ND — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000C585A6666ND — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated IEC 61800-3 category C3 control Integrated IEC 61800-3 category C4 Power
Protection functionsLine supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overvoltages on the DC bus drive Thermal overload for transformer drive Cabinet overheating drive Overcurrent drive Overload drive Short-circuit protection drive IGBT for each cell drive Thermal protection motor Motor phase break motor Motor earth fault motor Break on the control circuit drive Fan monitoring drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA 150 ms

Mechanical & Cooling

ATV6000C585A6666ND — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level83 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000C585A6666ND — Environmental
ParameterValue
Operating ambient temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport
Operating altitude3280.84...6561.68 ft (1000...2000 m) with derating factor
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature32...122 °F (0...50 °C)
Pollution degree2 IEC 61800-5-1

Approvals

ATV6000C585A6666ND — Approvals
ParameterValue
Certifications & markingCULus CE UKCA
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076 UL 347A

Communication

ATV6000C585A6666ND — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The ATV6000C585A6666ND is a Schneider Electric Altivar Process ATV6000 medium-voltage drive in a floor-standing enclosure, built around a 36-pulse diode rectifier bridge and IGBT inverter cells with multilevel PWM output. Rated for 4680 kW normal duty and 3740 kW heavy duty motor power, with corresponding line currents of 512 A and 406 A. The drive delivers an apparent power of 5850 kVA and a power factor of 96, with total harmonic current distortion (THDI) below 3% per IEEE 519-1992.

The heavy-duty current rating (406 A) is the figure to size cables and protection for continuous motor load; the normal-duty rating (512 A) applies when the drive is not expected to deliver full rated current continuously, such as in variable-torque fan/pump applications. Power losses are 177.2 kW at normal duty and 141.6 kW at heavy duty — that heat must be rejected by the forced-convection cooling system, and the enclosure's ventilation path needs clearance on both sides.

Compliance documentation includes CULus, CE, and UKCA markings, and the drive is designed to IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.

Physical configuration

The enclosure measures 124.06 in (3151 mm) high, 270.08 in (6860 mm) wide, and 70.9 in (1800 mm) deep — a substantial footprint that requires a dedicated equipment room or pad, not a standard panel. Cable entry is at the bottom, and the drive ships with the phase-shifting transformer, plinth, cooling fans, power cells, HMI, and medium-voltage arrestors included.

Frequently asked questions

What compliance documentation does this drive carry?

It carries CULus, CE, and UKCA markings and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, EN/IEC 60076, and UL 347A.

What are the key motor power and current ratings?

Normal duty: 4680 kW, 512 A line current. Heavy duty: 3740 kW, 406 A line current.

MPN