The ATV6000C782A6060NA3: This drive sits at the top of the ATV6000 line for high-power medium voltage applications. The 30-pulse rectifier design eliminates the need for external harmonic filters on most grids — the integrated THDI < 3% already meets IEEE 519-1992. The floor-standing enclosure (8260 mm wide, 3151 mm high, 1800 mm deep) houses power cells, phase-shifting transformer, cooling fans, and the 10-inch LCD HMI. Power losses run 236.6 kW at normal duty, 189.3 kW at heavy duty — plan for cabinet ventilation accordingly.
Cable entry is at the bottom. The control block provides two RJ45 ports for Ethernet IP / Modbus TCP and one RJ45 for Modbus serial. Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), and EtherCAT. Slot B handles encoder interface modules (5/12 V digital, analog, resolver, HTL). Digital I/O extension and output relay extension modules fit either slot. The 10-inch LCD touch screen is multi-language with an intuitive interface for commissioning and monitoring.