Skip to main content
Schneider Electric ATV6000D390A3333NA3 — AC Drive (VFD) 480V

Schneider ATV6000D390A3333NA3 Medium Voltage Drive, 390 kVA

MPNATV6000D390A3333NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000D390A3333NA3, medium voltage drive, 390 kVA apparent power, 310 kW normal duty / 240 kW heavy duty.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000D390A3333NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000D390A3333NA3 — Power & Output
ParameterValue
Motor power (kW)310 kW for normal duty 240 kW for heavy duty
Continuous output current65 A normal duty 52 A heavy duty
Max. transient current97.5 A during 3 s (normal duty) 97.5 A during 3 s (heavy duty)
Apparent power390 kVA

Input / Supply

ATV6000D390A3333NA3 — Input / Supply
ParameterValue
Rated supply voltage range3.3 kV +/- 10 %
Input line current68.3 A normal duty 53 A heavy duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for cooling fan 400 V AC +/- 10 % 3 kVA External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 %

Control & Performance

ATV6000D390A3333NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000D390A3333NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000D390A3333NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000D390A3333NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000D390A3333NA3 — Approvals
ParameterValue
Certifications & markingCE EAC
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000D390A3333NA3 — Communication
ParameterValue
Communication protocolsModbus serial Ethernet IP/Modbus TCP

Product details

The Schneider Electric ATV6000D390A3333NA3 is a medium-voltage drive from the Altivar Process ATV6000 series, rated for 390 kVA apparent power. It delivers 310 kW for normal-duty applications and 240 kW for heavy-duty cycles, making it a fit for pumps, fans, compressors, and conveyors in process industries like water/wastewater, mining, and oil & gas.

The 18-pulse diode rectifier input keeps harmonic distortion under 3% THDI, meeting IEEE 519-1992 without external filters — a real advantage when the facility has strict power-quality requirements or sensitive equipment on the same bus. The drive draws 68.3 A line current at normal duty and 53 A under heavy duty; the 18-pulse topology also improves input power factor to 0.96, reducing upstream transformer and cable sizing compared to a 6-pulse drive of the same kVA. Output voltage follows the supply voltage (no internal boost), and the IGBT inverter cells use multilevel PWM for clean motor waveforms — important for long cable runs or existing motor insulation systems. The drive handles permanent-magnet, synchronous, and asynchronous motors, so it's not locked into one motor technology.

Integration notes for the controls engineer

The drive ships in an IP-rated floor-standing enclosure (2460 mm wide, 2537 mm tall, 1400 mm deep) with cable entry at the bottom. Cooling is forced convection; the enclosure includes cabinet overheating protection and fan monitoring. The control block has two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial, plus slot A for a choice of PROFIBUS DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT communication modules. Slot B accepts encoder interfaces (digital 5/12 V, analog, resolver, or HTL). The 10-inch LCD touch screen provides multi-language local control and parameter access.

Frequently asked questions

What compliance documentation does this drive carry?

The drive is marked CE and EAC, and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076. The integrated EMC filter meets category C3 (control) and C4 (power) per IEC 61800-3.

What are the physical dimensions of this drive?

The floor-standing enclosure measures 2460 mm wide by 2537 mm tall by 1400 mm deep.

What motor types can this drive control?

It is designed for permanent-magnet, synchronous, and asynchronous motors.

What fieldbus options are available?

The drive has two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial. Slot A accepts communication modules for PROFIBUS DP V1, PROFINET, DeviceNet, CANopen (daisy chain RJ45, SUB-D 9, or screw terminals), or EtherCAT.

MPN
ATV6000D390A3333NA3