Skip to main content
Schneider Electric ATV6000D570A2424ND

Schneider ATV6000D570A2424ND AC Drive, 450 kW, 570 kVA

MPN ATV6000D570A2424ND
Active

Schneider Electric Altivar Process ATV6000 series, ATV6000D570A2424ND AC Drive (VFD), 450 kW normal duty / 410 kW heavy duty, 570 kVA, 3-phase, 480 V class, floor-standing enclosure.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ATV6000D570A2424ND specifications
ParameterValue
Input type54 pulse diode rectifier bridge
Display type10 inch LCD touch screen multi-language
Connector type2 RJ45 on the control block)Ethernet IP/Modbus TCP 1 RJ45 on the control block)Modbus serial
Current123.0 A heavy duty 155.4 A normal duty
Frequency50 Hz +/- 5 %
Phases3-phase
IP ratingIP31
Temp storage max50 °C
Temp storage min0 °C
Temp operating max60 °C
Temp operating min1.2 °C
Storage temperature32...122 °F (0...50 °C)
Pollution degreePollution degree 2
Operating temperature32...104 °F (0...40 °C) 104...122 °F (40...50 °C) with derating factor -13...158 °F (-25...70 °C) during transport

Product details

450 kW drive with integrated 54-pulse rectifier for low THDI

The ATV6000D570A2424ND is a floor-standing AC drive from the Altivar Process ATV6000 family, rated 450 kW normal duty and 410 kW heavy duty at 570 kVA apparent power. The 54-pulse diode rectifier input keeps total harmonic current distortion below 3 % per IEEE 519-1992, which means it meets utility grid-tie requirements without an external filter in most installations. Line current draws 155.4 A normal duty and 123.0 A heavy duty, with a power factor of 0.96. The IGBT inverter cells use multilevel PWM output voltage up to the supply voltage level — suitable for synchronous, asynchronous, and permanent magnet motors.

Control architecture and fieldbus options

Two option card slots (Slot A and Slot B) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, or EtherCAT, plus encoder interface modules (digital 5/12 V, analog, resolver, HTL) and I/O extension relays. The control block has two RJ45 ports for Ethernet IP/Modbus TCP and one for Modbus serial. The 10-inch LCD touch screen HMI is multi-language and ships with the drive. Configurable relay outputs (three total: one fault relay NO/NC, two sequence relays NO) handle status signalling.

Protection, compliance, and sourcing posture

Protection covers line supply over/undervoltage, phase loss, DC bus overvoltage, cabinet overheating, overcurrent, overload, short-circuit, IGBT cell faults, motor thermal/phase/earth faults, control circuit break, and fan monitoring. Standards include IEC 61800-3 (EMC categories C3 control, C4 power), IEC 61800-5-1, IEEE 519, and UL 347A. Markings: CULus, CE, UKCA.

MPN
ATV6000D570A2424ND