The ATV6000D630A1010NA3: Line current is 36.4 A normal duty, 29 A heavy duty — that's the input draw at the specified supply frequency (50 Hz ±5%). The output voltage is limited to whatever the supply delivers (no boost), so if your line runs low, expect proportional torque drop. Power losses run 21.9 kW normal duty, 17.5 kW heavy duty; that heat goes into the room via forced convection cooling, so the installation space needs ventilation rated for that dissipation.
The drive is designed for asynchronous, permanent magnet, and synchronous motors. The 48-pulse rectifier and integrated EMC filter (C3 control / C4 power) suit installations with strict harmonic and emissions requirements.