Skip to main content
Schneider Electric ATV6000D790A1111NA3 — AC Drive (VFD) 480V

Schneider ATV6000D790A1111NA3 AC Drive 600kW Heavy Duty

MPNATV6000D790A1111NA3
Active

Schneider Electric Altivar Process ATV6000D790A1111NA3, AC Drive (VFD) 480V, 600 kW heavy duty / 630 kW normal duty, 790 kVA, 54-pulse diode rectifier, floor-standing enclosure.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000D790A1111NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000D790A1111NA3 — Power & Output
ParameterValue
Motor power (kW)630 kW for normal duty 600 kW for heavy duty
Continuous output current39.6 A normal duty 38 A heavy duty
Max. transient current59.4 A during 3 s (normal duty) 71.3 A during 3 s (heavy duty)
Apparent power790 kVA

Input / Supply

ATV6000D790A1111NA3 — Input / Supply
ParameterValue
Rated supply voltage range11 kV +/- 10 %
Input line current40 A heavy duty 41.5 A normal duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA

Control & Performance

ATV6000D790A1111NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000D790A1111NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000D790A1111NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000D790A1111NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000D790A1111NA3 — Approvals
ParameterValue
Certifications & markingEAC CE
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000D790A1111NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

630 kW normal duty, 600 kW heavy duty — the real rating split

This ATV6000D790A1111NA3 is the big-frame Altivar Process drive rated 630 kW for normal duty and 600 kW for heavy duty, with a 790 kVA apparent power rating. Line current draw is 41.5 A normal duty, 40 A heavy duty, and the input is a 54-pulse diode rectifier bridge that keeps total harmonic current distortion below 3% per IEEE 519-1992. That means no external harmonic filter needed for most utility connections — the drive cleans its own draw.

Floor-standing enclosure — 4160 mm wide, 2751 mm tall, 1600 mm deep

This is not a panel-mount drive — it ships as a complete floor-standing enclosure (RAL 7035 light grey) with the phase-shifting transformer, power cells, cooling fans, HMI, and medium-voltage arrestors already integrated. You set it on the plant floor, land the incoming supply and motor cables through the bottom entry, and commission. Forced-convection cooling with integrated fans — the enclosure is sized for the thermal load; power losses run 27.4 kW at normal duty and 26.2 kW at heavy duty, so the room ventilation needs to handle that heat rejection.

Frequently asked questions

What motors does the ATV6000D790A1111NA3 support?

It is designed for asynchronous (induction) motors, permanent magnet synchronous motors, and synchronous reluctance motors — covers the three common types for pump, fan, compressor, and conveyor duty.

What compliance documentation does Schneider Electric provide for ATV6000D790A1111NA3?

The drive carries EAC and CE marking. It is designed to IEC 61800-3 (EMC), IEC 61800-4, IEC 61800-5-1 (safety), IEC 60529 (enclosure), IEEE 519:1992 (harmonic), and EN/IEC 60076 (transformer). The integrated EMC filter meets category C3 on the control side and C4 on the power side.