Skip to main content
Schneider Electric ATV6000D790A6060NA3 — AC Drive (VFD) 480V

Schneider ATV6000D790A6060NA3 Altivar Process Drive, 790 kVA

MPNATV6000D790A6060NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000D790A6060NA3, medium-voltage drive, 630 kW normal duty / 590 kW heavy duty, 790 kVA, 30-pulse diode rectifier.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000D790A6060NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000D790A6060NA3 — Power & Output
ParameterValue
Motor power (kW)630 kW for normal duty 590 kW for heavy duty
Continuous output current72.5 A normal duty 69 A heavy duty
Max. transient current109 A during 3 s (normal duty) 129 A during 3 s (heavy duty)
Apparent power790 kVA

Input / Supply

ATV6000D790A6060NA3 — Input / Supply
ParameterValue
Rated supply voltage range6 kV +/- 10 %
Input line current76.1 A normal duty 71 A heavy duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA

Control & Performance

ATV6000D790A6060NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000D790A6060NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000D790A6060NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000D790A6060NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000D790A6060NA3 — Approvals
ParameterValue
Certifications & markingCE EAC
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000D790A6060NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

Footprint and installation

The ATV6000D790A6060NA3: The enclosure measures 2760 mm wide by 2617 mm high by 1400 mm deep, light grey (RAL 7035), with bottom cable entry. Forced convection cooling keeps it running; noise level is 80 dB. The integrated EMC filter meets IEC 61800-3 category C3 on the control side and C4 on the power side.

Control and I/O

The 10-inch LCD touch screen provides multi-language HMI. Slot A accepts Profibus DP V1, PROFINET, DeviceNet, CANopen (RJ45, SUB-D 9, or screw terminals), or EtherCAT communication modules. Slot B handles digital/analog encoder interfaces (5/12 V, analog, resolver, HTL) or I/O extension modules. Eight programmable digital inputs (DI7, DI8 configurable as pulse inputs up to 30 kHz), configurable analog inputs (0–10 V or 0–20 mA, 12-bit), and configurable analog outputs (0–10 V or 0–20 mA, 10-bit) are standard.

Protection and compliance

Protection covers line supply over/undervoltage, phase loss, DC bus overvoltage, cabinet overheating, overcurrent, overload, short-circuit, motor thermal/phase/earth fault, and fan monitoring. Marked CE and EAC, compliant with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076. Pollution degree 2 per IEC 61800-5-1.

Frequently asked questions

What is the ATV6000D790A6060NA3's motor power rating?

It is rated for 630 kW normal duty and 590 kW heavy duty, with an apparent power of 790 kVA.

What compliance documentation does this drive carry?

It is marked CE and EAC, and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, IEEE 519:1992, and EN/IEC 60076.

What are the physical dimensions of the ATV6000D790A6060NA3?

The floor-standing enclosure is 2760 mm wide, 2617 mm high, and 1400 mm deep.

MPN
ATV6000D790A6060NA3