Skip to main content
Schneider Electric ATV6000D890A6060NA3 — AC Drive (VFD) 480V

Schneider ATV6000D890A6060NA3 ATV6000 Drive, 890 kVA, 710 kW

MPNATV6000D890A6060NA3
Active

Schneider Electric Altivar Process ATV6000, ATV6000D890A6060NA3, medium-voltage drive, 890 kVA, 710 kW normal duty, floor-standing enclosure.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6000D890A6060NA3 — Identification
ParameterValue
Product typeMedium voltage variable speed drive
Device short nameATV6000
Product range / familyAltivar Process ATV6000

Power & Output

ATV6000D890A6060NA3 — Power & Output
ParameterValue
Motor power (kW)710 kW for normal duty 670 kW for heavy duty
Continuous output current81.7 A normal duty 78 A heavy duty
Max. transient current123 A during 3 s (normal duty) 146 A during 3 s (heavy duty)
Apparent power890 kVA

Input / Supply

ATV6000D890A6060NA3 — Input / Supply
ParameterValue
Rated supply voltage range6 kV +/- 10 %
Input line current85.7 A normal duty 81 A heavy duty
Network number of phases3 phases
Internal/auxiliary suppliesInternal supply for digital inputs and PoE 24 V DC 21...27 V, Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, External supply for digital inputs 24 V DC 19...30 V External supply for control circuit 100...240 V AC 47...63 Hz External supply for control circuit 120...370 V DC +/- 10 % 1 kVA Auxiliary power supply 230 V AC +/- 10 % External supply for cooling fan 400 V AC +/- 10 % 7 kVA

Control & Performance

ATV6000D890A6060NA3 — Control & Performance
ParameterValue
Output frequency range0.1...120 Hz
Asynchronous motor control modesClosed loop vector control U/F vector control Energy saving control Vector control with slip compensation in open loop
Synchronous motor control modesPermanent magnet control in open loop Permanent magnet control in close loop Line start permanent magnet motor

Protection & EMC

ATV6000D890A6060NA3 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated conforming to IEC 61800-3 category C3 control Integrated conforming to IEC 61800-3 category C4 power
Protection functionsLine supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overvoltages on the DC bus: drive Thermal overload for transformer: drive Cabinet overheating: drive Overcurrent: drive Overload: drive Short-circuit protection: drive IGBT for each cell: drive Thermal protection: motor Motor phase break: motor Motor earth fault: motor Break on the control circuit: drive Fan monitoring: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)31.5 kA for 150 ms

Mechanical & Cooling

ATV6000D890A6060NA3 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP31 conforming to IEC 60529
Acoustic noise level80 dB
Cooling methodForced convection
Assembly / installation styleIn floor-standing enclosure

Environmental

ATV6000D890A6060NA3 — Environmental
ParameterValue
Operating ambient temperature0...40 °C 40...50 °C with derating factor -25...70 °C during transport
Operating altitude1000...2000 m with derating factor
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature0...50 °C
Pollution degree2 conforming to IEC 61800-5-1

Approvals

ATV6000D890A6060NA3 — Approvals
ParameterValue
Certifications & markingCE EAC
Standards complianceIEC 61800-3 EN/IEC 61800-4 IEC 61800-5-1 IEC 60529 IEEE 519:1992 EN/IEC 60076

Communication

ATV6000D890A6060NA3 — Communication
ParameterValue
Communication protocolsEthernet IP/Modbus TCP

Product details

The Schneider Electric ATV6000D890A6060NA3 is a medium-voltage Altivar Process ATV6000 drive rated for 890 kVA apparent power, delivering 710 kW for normal duty and 670 kW for heavy duty induction, synchronous, or permanent magnet motors. The input stage uses a 30-pulse diode rectifier bridge, keeping total harmonic current distortion (THDI) below 3% per IEEE 519-1992 without an external filter. It ships in a floor-standing enclosure (2760 mm wide × 2617 mm high × 1400 mm deep) with integrated phase-shifting transformer, power cells, cooling fans, and a 10-inch LCD touch screen HMI.

Integration notes

Two option card slots (A and B) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, CANopen, EtherCAT, or I/O and relay extensions. The control block includes two RJ45 ports for Ethernet IP/Modbus TCP and one RJ45 for Modbus serial. Eight programmable digital inputs (24 V DC, two configurable as pulse inputs up to 30 kHz) and configurable analog inputs (0–10 V or 0–20 mA, 12-bit) handle the control interface. Three relay outputs (one NO/NC fault, two NO sequence) are standard. Electrical isolation between power and control circuits is maintained. The drive meets IEC 61800-3, IEC 61800-4, IEC 61800-5-1, and IEC 60529; the integrated EMC filter conforms to category C3 (control) and C4 (power).

Ratings & protection

Line current is 85.7 A normal duty / 81 A heavy duty. Power losses are 30.9 kW (normal) and 29.2 kW (heavy). Forced convection cooling keeps the enclosure within ratings; noise level is 80 dB. Protection covers line supply overvoltage/undervoltage/phase loss, DC bus overvoltage, transformer thermal overload, cabinet overheating, overcurrent, overload, short-circuit, motor phase break, motor earth fault, and fan monitoring.

Frequently asked questions

What are the key ratings of the ATV6000D890A6060NA3?

Apparent power is 890 kVA, motor power is 710 kW for normal duty and 670 kW for heavy duty. Line current is 85.7 A normal / 81 A heavy.

What compliance standards does the ATV6000D890A6060NA3 meet?

It is marked CE and EAC, and complies with IEC 61800-3, IEC 61800-4, IEC 61800-5-1, IEC 60529, and IEEE 519:1992.

MPN
ATV6000D890A6060NA3