Schneider Electric ATV630C22N4US — AC Drive (VFD) 480V

Schneider ATV630C22N4US Altivar Drive, 427 A ND

MPNATV630C22N4US
Active

Schneider Electric Altivar Process ATV630 variable speed drive, ATV630C22N4US, 380-480 V, 220 kW normal duty (160 kW heavy duty), 427 A nominal output, standard version, CE marked.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV630C22N4US — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV630
Product range / familyAltivar Process ATV600
ATV630C22N4US — Power & Output
ParameterValue
Motor power (kW)160 kW heavy duty) 220 kW normal duty)
Continuous output current302 A 2.5 kHz heavy duty 427 A 2.5 kHz normal duty
ATV630C22N4US — Input / Supply
ParameterValue
Rated supply voltage range380...480 V
Input line current397 A 380 V normal duty) 324 A 480 V normal duty) 296 A 380 V heavy duty) 246 A 480 V heavy duty)
ATV630C22N4US — Control & Performance
ParameterValue
Output frequency range0.1...500 Hz
ATV630C22N4US — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 164.04 ft (50 m) IEC 61800-3 category C3
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
ATV630C22N4US — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00IEC 61800-5-1 IP00IEC 60529 IP21 with kit VW3A9112)IEC 61800-5-1 IP21 with kit VW3A9112)IEC 60529
Acoustic noise level73 dB
Cooling methodForced convection
ATV630C22N4US — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) (without derating) 104...140 °F (40...60 °C) (with derating factor)
Operating altitude3280.84...9842.52 ft (1000...3000 m) with current derating 1 % per 100 m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-13...158 °F (-25...70 °C)
Pollution degree2
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV630C22N4US — Approvals
ParameterValue
Certifications & markingCE
Standards complianceUL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATV630C22N4US — Communication
ParameterValue
Communication protocolsModbus TCP Ethernet Modbus serial

Product details

The ATV630C22N4US is a current-production Altivar Process ATV630 variable speed drive from Schneider Electric, rated for 220 kW normal duty (160 kW heavy duty) on a 380-480 V supply, with a nominal output current of 427 A. It supports both asynchronous and synchronous motors and delivers an output frequency range of 0.1-500 Hz. This standard-version drive includes integrated EMC filter for IEC 61800-3 Category C3 (effective up to 50 m cable) and carries CE marking, UL 508C, and TAA/BAA compliance via COTS.

Mounting and integration constraints

Wall-mount only, vertical orientation within ±10 degrees. Forced convection cooling moves 860 m³/h of air; sound pressure at 73 dB. The drive ships as IP00; an IP21 kit (VW3A9112) is available separately. Ambient conditions: 5–95% relative humidity without condensation, altitude up to 1000 m (derate 1% per 100 m above that). Vibration resistance per IEC 60068-2-6: 1.5 mm peak-to-peak at 2–13 Hz, 1 gn at 13–200 Hz. Shock rated at 15 gn for 11 ms per IEC 60068-2-27.

Options, safety, and compliance

The drive is equipped with one option slot (Slot A) for communication modules (PROFIBUS DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, BACnet MS/TP, Ethernet Powerlink) and a shared Slot A/B for I/O extension and output relay modules. Integrated safety includes STO (Safe Torque Off) rated SIL 3. Standard Modbus serial plus Ethernet (Modbus TCP) ports are on-board. The drive holds pollution degree 2, overvoltage category III, and complies with IEC 61800-3 environment 1 category C2 and environment 2 category C3. Total harmonic current distortion remains below 48% at full load per IEC 61000-3-12.

Frequently asked questions

What markings and variant does this drive carry?

The drive is CE marked and is the Standard version of the Altivar Process ATV630 range.

What compliance documentation does this drive support?

It is UL 508C listed, meets IEC 61800-3 (environments C2/C3), IEC 61800-5-1, IEC 61508, and IEC 13849-1. It also carries TAA and BAA compliance via COTS, making it suitable for US federal procurement.

MPN