Drive Selection Brief
The Schneider Electric ATV630D22M3US is an Altivar Process ATV630 variable speed drive rated 22 kW normal duty (18.5 kW heavy duty) for 200-240 V three-phase supply. Continuous output current is 92.6 A at 4 kHz for normal duty, derated to 78.4 A for heavy duty applications requiring higher torque margin. This variant ships without an internal EMC filter, so external filtering or a line reactor will be needed to meet conducted emissions limits under IEC 61800-3 environment 2 category C3 or environment 1 category C2. Safety function STO (Safe Torque Off) is integrated to SIL 3, eliminating external safety relays for deceleration-related hazards.
Compliance documentation covers UL 508C, IEC 61800-3, and TAA BABA BAA via COTS, per the listing.
Integration Notes
Wall-mount rated IP21, forced convection cooling requiring 240 m³/h clearance around the heatsink. Slot A accepts fieldbus modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, Ethernet Powerlink, and BACnet MS/TP. Slot A/B also accepts I/O extension or relay output modules. Eight discrete inputs, two configurable as pulse inputs up to 30 kHz; integrated PID regulator for process control loops. Operating altitude up to 4800 m with 1 % derating per 100 m above 1000 m; vibration resistance 1.5 mm peak-to-peak at 2-13 Hz.