Schneider Electric ATV630D22N4US — AC Drive (VFD) 480V

Schneider ATV630D22N4US Altivar Process Drive, 22 kW, 380-48

MPNATV630D22N4US
Active

Schneider Electric Altivar Process ATV630, standard version, 22 kW normal duty / 18.5 kW heavy duty, 380…480 V, IP21, wall-mount drive.

$5,458.38Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV630D22N4US — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV630
Product range / familyAltivar Process ATV600
ATV630D22N4US — Power & Output
ParameterValue
Motor power (kW)22 kW normal duty) 18.5 kW heavy duty)
Continuous output current46.3 A 4 kHz normal duty 39.2 A 4 kHz heavy duty
ATV630D22N4US — Input / Supply
ParameterValue
Rated supply voltage range380...480 V
Input line current39.6 A 380 V normal duty) 34.4 A 480 V normal duty) 34.1 A 380 V heavy duty) 29.9 A 480 V heavy duty)
ATV630D22N4US — Control & Performance
ParameterValue
Output frequency range0.1...500 Hz
ATV630D22N4US — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 164.04 ft (50 m) IEC 61800-3 category C2 Integrated 492.1 ft (150 m) IEC 61800-3 category C3
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
ATV630D22N4US — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1 UL 508C
IP degree of protectionIP21IEC 61800-5-1 IP21IEC 60529
Acoustic noise level59.5 dB
Cooling methodForced convection
ATV630D22N4US — Environmental
ParameterValue
Operating ambient temperature5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV630D22N4US — Approvals
ParameterValue
Certifications & markingCE
Standards complianceUL 508C IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATV630D22N4US — Communication
ParameterValue
Communication protocolsModbus TCP Ethernet Modbus serial

Product details

The ATV630D22N4US is a standard-version variable speed drive from the Altivar Process ATV600 series, sized for 22 kW normal-duty or 18.5 kW heavy-duty induction or synchronous motors on a 380…480 V three-phase supply. Normal-duty continuous output is 46.3 A at 4 kHz; heavy-duty continuous output is 39.2 A at 4 kHz — the 4 kHz switching frequency is the default for most fan/pump profiles, and the drive delivers full rated current at that frequency without derating. The integrated EMC filter meets IEC 61800-3 category C2 for 50 m motor cable and category C3 for 150 m, covering most industrial installations without an external filter.

Integration notes

Wall-mount only — vertical within ±10° of plumb. Forced-convection cooling draws 215 m³/h; leave clearance above and below for airflow. The IP21 enclosure (UL type 1) is suitable for clean, dry indoor environments; if washdown or dust is present, plan for a higher-degree enclosure or cabinet. Accepts plug-in option cards in Slot A for fieldbus (Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen, Ethernet Powerlink, BACnet MS/TP) and I/O or relay extension in Slot A or B. The eight discrete inputs include two programmable as pulse inputs up to 30 kHz for encoder or flowmeter feedback. Adjustable PID regulator is built in — no external controller needed for pressure, level, or flow loops. Harmonic distortion (THDI) stays below 48 % from 80 to 100 % load per IEC 61000-3-12, which keeps line pollution within typical utility limits without an external line reactor for most installations.

Frequently asked questions

What safety functions does this drive include?

STO (Safe Torque Off) rated SIL 3 per IEC 61508 and IEC 13849-1 is integrated. This allows the drive to safely remove torque without an external contactor for most stop functions.

What communication protocols can be added?

Slot A accepts fieldbus option cards for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (RJ45, SUB-D 9, or screw terminals), Ethernet Powerlink, and BACnet MS/TP. Modbus serial and Modbus TCP are also embedded on the base unit.

What is the supply voltage range and frequency?

Rated supply voltage is 380…480 V AC, 50/60 Hz ±5 %. The drive is designed for three-phase industrial mains.

What compliance documentation is available?

The drive carries CE marking and complies with UL 508C, IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508, and IEC 13849-1 (functional safety). It is also TAA/BAA compliant via COTS.