Schneider Electric ATV650D90N4428
MPNATV650D90N4428
Active
variable speed drive, Altivar Process ATV600, ATV650, 90kW, 125hp, 380...480V, IP55, marine certification
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Variable speed drive |
| Device short name | ATV650 |
| Product range / family | Altivar Process ATV600 |
Power & Output
| Parameter | Value |
|---|---|
| Motor power (kW) | 55 kW (heavy duty) 90 kW (normal duty) |
| Continuous output current | 106 A at 2.5 kHz for heavy duty 173 A at 2.5 kHz for normal duty |
Input / Supply
| Parameter | Value |
|---|---|
| Rated supply voltage range | 380...480 V |
| Input line current | 112.7 A at 480 V (normal duty) 98.9 A at 380 V (heavy duty) 86.9 A at 480 V (heavy duty) 156.2 A at 380 V (normal duty) |
Control & Performance
| Parameter | Value |
|---|---|
| Output frequency range | 0.1...500 Hz |
Protection & EMC
| Parameter | Value |
|---|---|
| Integrated EMC filter class | Integrated with 150 m conforming to IEC 61800-3 category C3 |
| EMC immunity tests | Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 |
Mechanical & Cooling
| Parameter | Value |
|---|---|
| IP degree of protection | IP55 conforming to IEC 60529 IP55 conforming to IEC 61800-5-1 |
| Acoustic noise level | 69.9 dB |
| Cooling method | Forced convection |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | 40...50 °C (with derating factor) -15...40 °C (without derating) |
| Operating altitude | 1000...4800 m with current derating 1 % per 100 m <= 1000 m without derating |
| Relative humidity | 5...95 % without condensation conforming to IEC 60068-2-3 |
| Storage / transport temperature | -40...70 °C |
| Pollution degree | 3 |
| Vibration resistance | 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6 1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 |
Approvals
| Parameter | Value |
|---|---|
| Certifications & marking | CE |
| Standards compliance | IEC 61800-3 IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 508C |
Communication
| Parameter | Value |
|---|---|
| Communication protocols | Modbus TCP Modbus serial Ethernet |
MPN