Schneider Electric ATV6A0C11R4 — AC Drive (VFD) 480V

Schneider ATV6A0C11R4 Altivar Process Drive, 110 kW

MPNATV6A0C11R4
Active

Schneider Electric Altivar Process ATV600 series, ATV6A0C11R4 modular drive, 110 kW at 440 V normal duty, 90 kW heavy duty.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C11R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C11R4 — Power & Output
ParameterValue
Motor power (kW)110.0 kW at 440 V normal duty 90.0 kW at 440 V heavy duty
Continuous output current211.0 A at 2.5 kHz normal duty 173.0 A at 2.5 kHz heavy duty
Max. transient current232.1 A during 60 s (normal duty) 259.5 A during 60 s (heavy duty)
Apparent power139 kVA at 440 V normal duty 118 kVA at 440 V heavy duty

Input / Supply

ATV6A0C11R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current183.0 A at 440 V (normal duty) 155.0 A at 440 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), <200 mA, protection type: overload and short-circuit protection

Control & Performance

ATV6A0C11R4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C11R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C11R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level69 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C11R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C11R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C11R4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The ATV6A0C11R4 is a modular Altivar Process drive from the ATV600 series, rated 110 kW at 440 V normal duty and 90 kW heavy duty. It ships as a kit with the power module, control unit, mounting hardware and fuse set. The integrated EMC filter holds C3 compliance for 300 m cable runs; if your installation exceeds that or demands C2, expect external filtering.

Control wiring and supply constraints

Digital inputs require external 24 V DC (19-30 V). Internal supply for digital inputs and STO provides 24 V DC (21-27 V) at under 200 mA with short-circuit protection.

Lifecycle status is current. The drive complies with IEC 61800-3, -5-1, -5-2, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1. Marking is CE.

Frequently asked questions

What are the supply voltage requirements for the digital inputs and STO?

External supply for digital inputs is 24 V DC (19...30 V). Internal supply for digital inputs and STO is 24 V DC (21...27 V) at under 200 mA with overload and short-circuit protection.

What marking does the ATV6A0C11R4 carry?

CE marking.

What compliance standards does this drive meet?

It complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

MPN
ATV6A0C11R4