Skip to main content
Schneider Electric ATV6A0C11T4 — AC Drive (VFD) 480V

Schneider ATV6A0C11T4 Process Drive, 110 kW, STO SIL3

MPNATV6A0C11T4
Active

Schneider Altivar Process ATV600, ATV6A0C11T4, modular drive, 110 kW normal duty (150 hp) at 480 V, STO SIL3, integrated EMC filter category C3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C11T4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C11T4 — Power & Output
ParameterValue
Motor power (kW)110.0 kW at 480 V normal duty 90.0 kW at 480 V heavy duty
Continuous output current211.0 A at 2.5 kHz normal duty 173.0 A at 2.5 kHz heavy duty
Max. transient current232.1 A 60 s normal duty) 259.5 A 60 s heavy duty)
Apparent power140 kVA at 480 V normal duty 121 kVA at 480 V heavy duty

Input / Supply

ATV6A0C11T4 — Input / Supply
ParameterValue
Rated supply voltage range480 V - 15...10 %
Input line current168.0 A 480 V normal duty) 145.0 A 480 V heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protection

Control & Performance

ATV6A0C11T4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C11T4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C11T4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Acoustic noise level69 dB 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C11T4 — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2 IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C11T4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C11T4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

What this drive delivers

The Schneider Altivar Process ATV6A0C11T4 is an active-production modular drive rated 110 kW normal duty (150 hp) at 480 V, with heavy-duty 90 kW (125 hp) capability. It integrates STO SIL3 and a C3 EMC filter for 300 m cable runs. Line current pulls 168 A at 480 V normal duty, 145 A heavy duty, so panel feed and branch protection follow those numbers. Apparent power sits at 140 kVA normal duty.

Mounting and supply requirements

Cabinet mount, forced-convection cooled. The control section needs a 24 V DC external supply for digital inputs (19...30 V), plus internal 24 V for STO and digital inputs (21...27 V) with <200 mA short-circuit protection. An internal 10.5 V DC reference supply handles a 1 to 10 kOhm potentiometer. Analog inputs are software-configurable for 0-10 V or 0/4-20 mA with 12-bit resolution; accuracy holds ±0.6% over a 60 °C temperature variation. Six discrete inputs are programmable, with two capable of pulse inputs up to 30 kHz. Relay outputs R1 (fault) and R2, R3 (sequence) are configurable, rated 5 ms ±0.5 ms refresh. Slot A accepts communication modules for Profibus, PROFINET, DeviceNet, Modbus TCP, or CANopen.

Frequently asked questions

What supply voltages are required for the control section?

Digital inputs need an external 24 V DC supply (19...30 V). STO and internal digital input supply is also 24 V DC (21...27 V) with <200 mA short-circuit protection. A separate 10.5 V DC reference is provided for a potentiometer (1 to 10 kOhm).

What safety function does this drive support?

Safe Torque Off (STO) rated SIL 3, integrated into the drive.

Which compliance standards does it meet?

CE marked, conforms to IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), IEC 61508 (functional safety), and IEC 13849-1.

MPN
ATV6A0C11T4