Skip to main content
Schneider Electric ATV6A0C13T4 — AC Drive (VFD) 480V

Schneider ATV6A0C13T4 Altivar Process ATV600, 132 kW

MPNATV6A0C13T4
Active

Schneider Altivar Process ATV600 ATV6A0C13T4, modular cabinet drive, 132 kW / 200 hp at 480 V, STO SIL3, integrated EMC filter C3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C13T4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C13T4 — Power & Output
ParameterValue
Motor power (kW)132.0 kW at 480 V normal duty 110.0 kW at 480 V heavy duty
Continuous output current250.0 A at 2.5 kHz normal duty 211.0 A at 2.5 kHz heavy duty
Max. transient current275 A 60 s normal duty) 316.5 A 60 s heavy duty)
Apparent power181 kVA at 480 V normal duty 140 kVA at 480 V heavy duty

Input / Supply

ATV6A0C13T4 — Input / Supply
ParameterValue
Rated supply voltage range480 V - 15...10 %
Input line current218.0 A 480 V normal duty) 168.0 A 480 V heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), <200 mA overload and short-circuit protection

Control & Performance

ATV6A0C13T4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C13T4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C13T4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Acoustic noise level69 dB 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C13T4 — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2 IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C13T4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C13T4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The Schneider ATV6A0C13T4 is a 132 kW (200 hp normal duty at 480 V) Altivar Process ATV600 variable speed drive in a modular cabinet format. It carries Safe Torque Off (STO) rated SIL3 per IEC 61508, and an integrated EMC filter classified C3 for cable runs up to 300 m. Control supply needs a separate 24 V DC source (19...30 V for digital inputs; 21...27 V for STO and internal logic), plus an internal 10.5 V DC reference for a 1–10 kΩ potentiometer — all protected against overload and short circuit up to 200 mA.

Mounting and wiring quick check

Cabinet-mounted, forced-convection cooled, pollution degree 2. Digital inputs DI1–DI6 are 24 V DC programmable (DI5, DI6 also accept pulse inputs up to 30 kHz). Analog inputs AI1–AI3 are software-configurable for voltage (0–10 V DC, 30 kΩ) or current (0–20 mA, 250 Ω). Relay outputs R1 (fault) and R2, R3 (sequence) are configurable NO/NC rated 100,000 cycles. The drive accepts optional communication modules on slot A (Profibus DP, PROFINET, DeviceNet, Modbus TCP, CANopen, I/O extension) and slot B (I/O or relay extension). For Ethernet variants, speed is 10/100 Mbit/s, half/full duplex auto-negotiation.

Frequently asked questions

What are the supply voltage requirements for the ATV6A0C13T4?

It requires an external 24 V DC supply (19...30 V) for digital inputs, a separate 24 V DC (21...27 V) for digital inputs and STO, and provides an internal 10.5 V DC output for a reference potentiometer (1 to 10 kΩ). All supplies are protected against overload and short circuit at <200 mA.

What is the ATV6A0C13T4's marking?

It carries CE marking.

What compliance standards does the ATV6A0C13T4 meet?

It complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonics), IEC 60721-3 (environmental), and functional safety standards IEC 61508 and IEC 13849-1 for STO SIL3.

MPN
ATV6A0C13T4