Specifications

ATV6A0C16S6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6A0
Product / component typeVariable speed drive
ATV6A0C16S6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 15...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current152.0 A 600 V normal duty) 131.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % full load IEC 61000-3-12
ATV6A0C16S6 — Output / Performance
ParameterValue
Apparent power158 kVA at 600 V normal duty 136 kVA at 600 V heavy duty
Continuous output current175.0 A at 2.5 kHz normal duty 145.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6A0C16S6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6A0C16S6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6A0C16S6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level69 dB 86/188/EEC
ATV6A0C16S6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

Cabinet mounting and power connections

The Schneider Electric ATV6A0C16S6 is a modular cabinet-mount variable frequency drive in the Altivar Process ATV600 series. It is rated for 175 hp at 600 V normal duty, with a corresponding line current of 152 A and apparent power of 158 kVA. The heavy-duty rating is 150 hp, 131 A at 600 V. The drive accepts a supply frequency of 50 to 60 Hz, and the switching frequency is adjustable from 2 to 4.9 kHz with derating. An integrated EMC filter complying with IEC 61800-3 category C3 (300 m cable) saves panel space and external filter costs. Line-side and motor connections use screw terminals; the motor connection is via M10 bars. The drive includes a power connection set of fuses and mechanical mounting kits in the kit composition. Enclosure rating is UL type 1 for cabinet integration, assuming proper ventilation given forced-convection cooling.

Fieldbus slot and safety loop

Two option card slots (A and B) accept communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D 9, or screw terminals). The drive ships with a Modbus serial slave interface (2-wire RS-485, RTU frame, addresses 1–247) and a Modbus TCP slave port (10/100 Mbit/s, half/full duplex, auto-negotiation). For OEMs migrating from legacy fieldbuses, slot A retains the PROFINET or Profibus option without removing the integrated serial port. Safe torque off (STO) is integrated to SIL 3, which reduces external safety relay hardware for simple stop functions. The drive also monitors motor phase break, overspeed, DC bus overvoltages, line supply phase loss, and ground faults. That protection suite covers both the drive and the motor.

The drive carries CE marking and complies with IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic limits), IEC 60721-3 (environmental), IEC 61508 and IEC 13849-1 (functional safety), and UL 61800-5-1. Pollution degree 2, altitude up to 2000 m with current derating above 1000 m, and shock resistance 4 gn / 11 ms. Vibration resistance: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz.

Frequently asked questions

What is the ATV6A0C16S6's listed marking and variant?

Marking is CE, and the variant is a modular version designed for cabinet mounting.

What compliance documentation does Schneider provide for this drive?

The drive complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1. The integrated EMC filter meets category C3. RoHS and REACH compliance is standard for Schneider Altivar products.

How do I source the ATV6A0C16S6?

It is quoted to order against an RFQ through our distribution channel. Lead time and pricing depend on quantity and current factory availability.

MPN