Skip to main content
Schneider Electric ATV6A0C16T6 — AC Drive (VFD) 600V

Schneider Altivar ATV6A0C16T6 VFD, 150-175 hp, 600 V

MPNATV6A0C16T6
Active

Schneider Electric Altivar Process ATV600, modular VFD, ATV6A0C16T6, 150-175 hp at 600 V, 152/131 A line current, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6A0C16T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6A0
Product / component typeVariable speed drive
ATV6A0C16T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 15...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current152.0 A 600 V normal duty) 131.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % full load IEC 61000-3-12
ATV6A0C16T6 — Output / Performance
ParameterValue
Apparent power158 kVA at 600 V normal duty 136 kVA at 600 V heavy duty
Continuous output current175.0 A at 2.5 kHz normal duty 145.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6A0C16T6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6A0C16T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6A0C16T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level69 dB 86/188/EEC
ATV6A0C16T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

The Schneider Altivar Process ATV600 ATV6A0C16T6 is a modular VFD rated for 150 hp heavy duty or 175 hp normal duty at 600 V, drawing 131 A or 152 A line current respectively. Apparent power comes in at 136 kVA heavy duty, 158 kVA normal duty. It ships as a kit: control unit, mechanical mounting kit, power connection set of fuses, and a 200 kW power module. The integrated EMC filter meets IEC 61800-3 category C3 for 300 m motor cable runs. That means it's suited for industrial second-environment installations where conducted emissions are a concern, but not for residential or first-environment without additional filtering. Lifecycle status is current production — this is not an NRND or obsolete line. No last-time-buy clock ticking here.

The 131 A heavy-duty line current at 600 V is the number to size your input conductors and protective devices against for continuous motor load. The 152 A normal-duty figure applies when the load profile is lighter — pump or fan curves, not constant torque. Prospective line Isc is 50 kA, so the upstream breaker or fuse must have an interrupting rating that covers that fault current at the drive's supply point. Switching frequency is adjustable from 2 to 4.9 kHz with derating. If you're running long motor cables or trying to quiet an audible whine, expect to derate output current at the higher end. The drive handles both synchronous and asynchronous motors, and braking to standstill is by DC injection — no built-in dynamic braking resistor, so plan for an external resistor if you need rapid deceleration or vertical loads. The modular variant means the power module and control unit are separate; the kit includes both plus the mounting hardware. Slot A and Slot B accept option cards for fieldbus (Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen) or digital/analog I/O and relay extension. The base unit ships with a 2-wire RS 485 Modbus serial port (RTU, 4.8 to 38.4 kbit/s) and a Modbus TCP slave on a 10/100 Mbit/s Ethernet port.

Cabinet-mount only. The drive is UL Type 1 and Type 12 compliant for cabinet integration — that means it's not a standalone enclosure; it goes inside a panel. Forced-convection cooling, so ensure clearance around the heatsink. Pollution degree 2 per IEC 61800-5-1, which is typical for a controlled environment. Ambient conditions: 5 to 95% relative humidity without condensation, vibration resistance 1.5 mm peak-to-peak at 2–13 Hz and 0.5 gn at 13–200 Hz, shock 4 gn for 11 ms. Supply frequency is 50/60 Hz ±5%. Line connections are screw terminals on the line side and M10 bars on the motor side; control wiring uses removable screw terminals accepting 0.5 to 1.5 mm² (AWG 20 to 16).

Current production — no phase-out or NRND flag. The ATV6A0C16T6 is a standard catalog item carrying CE marking and compliance with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1. The integrated EMC filter keeps total harmonic current distortion below 48% at full load per IEC 61000-3-12. Noise level is 69 dB per 86/188/EEC.

Frequently asked questions

What is the closest alternative to ATV6A0C16T6 in the same family?

There is no direct pin-compatible or drop-in alternative within the ATV600 series. The ATV6A0C16T6 is the specific 200 kW modular variant with integrated C3 EMC filter. A different EMC category or non-modular chassis would be a different order code.

What compliance documentation does this drive carry?

CE marking, plus compliance with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and UL 61800-5-1.

What are the key ratings for this VFD?

150 hp heavy duty / 175 hp normal duty at 600 V, line current 131 A heavy duty / 152 A normal duty, apparent power 136 kVA heavy duty / 158 kVA normal duty, integrated EMC filter C3, STO SIL 3.

How do I source this drive?

It is a current-production catalog item, sourced to order against an RFQ. No last-time-buy or surplus channel needed.

MPN
ATV6A0C16T6