Building the BOM around this drive
Cabinet mount only — no through-panel gland plate kit in the box. The kit includes one control unit, one power module (200 kW size), mechanical mounting hardware, and a set of fuses. Line-side connection uses M10 screw bars; control uses removable screw terminals 0.5–1.5 mm² (AWG 20–16). Cooling is forced convection; ambient derating above 40 °C (not stated explicitly but typical for this range). Operating altitude up to 1000 m without derating; above that, reduce current per the drive's thermal curve. Pollution degree 2 per IEC 61800-5-1, so standard office/light industrial environment acceptable. Safe torque off (STO) certified to SIL 3 — no need for an external safety relay if the control system provides a dual-channel STO signal. Motor protection includes thermal, phase break, short-circuit, and ground fault detection. Communication slot A accepts fieldbus modules for PROFIBUS DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen. The base drive includes Modbus serial (RS-485, 2-wire, RTU) and Modbus TCP (Ethernet). If the control network is one of those, no extra module needed.