Skip to main content
Schneider Electric ATV6A0C25R4 — AC Drive (VFD) 480V

Schneider ATV6A0C25R4 Altivar Process Drive, 250 kW

MPNATV6A0C25R4
Active

Schneider Altivar Process ATV600, ATV6A0C25R4, 250 kW normal duty at 440 V, modular version, integrated EMC filter C3, STO SIL3.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C25R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C25R4 — Power & Output
ParameterValue
Motor power (kW)250.0 kW at 440 V normal duty 200.0 kW at 440 V heavy duty
Continuous output current477.0 A at 2.5 kHz normal duty 370.0 A at 2.5 kHz heavy duty
Max. transient current524.7 A during 60 s (normal duty) 555 A during 60 s (heavy duty)
Apparent power302 kVA at 440 V normal duty 248 kVA at 440 V heavy duty

Input / Supply

ATV6A0C25R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current396.0 A at 440 V (normal duty) 325.0 A at 440 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), <200 mA, protection type: overload and short-circuit protection

Control & Performance

ATV6A0C25R4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C25R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C25R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level70 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C25R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C25R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C25R4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

Drive for conveyor zones

The ATV6A0C25R4: Heavy duty rating drops to 200 kW at 440 V, which gives you constant-torque headroom for a screw conveyor or belts under high breakaway load. Apparent power at normal duty is 302 kVA, heavy duty 248 kVA.

This drive carries a current lifecycle stage — no end-of-life notice active. CE marking is on the nameplate, and standards compliance includes IEC 61800-3, IEC 61508 (SIL 3 for STO), and IEC 13849-1. Documentation pack covers the declaration of conformity per Schneider's standard.

The ATV6A0C25R4 is a modular version shipped as a kit: control unit, two 160 kW power modules, mechanical mounting parts, connection set, and front cover. Cabinet mount, forced-convection cooling. Slot A accepts Profibus, PROFINET, DeviceNet, or CANopen; slot A/B also accept I/O or relay extension modules. Analog inputs AI1–AI3 are 12-bit, software-configurable voltage or current, with sampling every 5 ms. Fast digital inputs DI1–DI4 sample at 2 ms. STO inputs are 24 V DC with <200 mA total draw.

Duty ratings for conveyor loads

Normal duty (250 kW at 440 V, 396 A line current, 302 kVA) is sized for variable-torque applications like fan or pump-drive conveyors. Heavy duty (200 kW at 440 V, 325 A line current, 248 kVA) covers constant-torque loads — think pallet conveyors or screw feeders. THDI stays under 48% at full load.

Frequently asked questions

What are its supply requirements?

External 24 V DC (19...30 V) for digital inputs. Internal 10.5 V DC ±5% for the reference potentiometer. Internal 24 V DC (21...27 V) for digital inputs and STO, with overload and short-circuit protection.

What communication interfaces are built in?

Modbus serial (2-wire RS-485, RTU, 4.8–38.4 kbps) and Modbus TCP (10/100 Mbit/s, half/full duplex). Slot A accepts Profibus, PROFINET, DeviceNet, CANopen, or Ethernet/IP modules.

MPN
ATV6A0C25R4