Skip to main content
Schneider Electric ATV6A0C31T6 — AC Drive (VFD) 600V

Schneider ATV6A0C31T6 Altivar Process 600, 350 HP

MPNATV6A0C31T6
Active

Schneider Altivar Process ATV600, modular, ATV6A0C31T6, 350 hp at 600 V normal duty, 250 hp heavy duty, STO SIL3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6A0C31T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6A0
Product / component typeVariable speed drive
ATV6A0C31T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 15...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current298.0 A 600 V normal duty) 218.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % full load IEC 61000-3-12
ATV6A0C31T6 — Output / Performance
ParameterValue
Apparent power310 kVA at 600 V normal duty 227 kVA at 600 V heavy duty
Continuous output current340.0 A at 2.5 kHz normal duty 275.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6A0C31T6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6A0C31T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6A0C31T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level70 dB 86/188/EEC
ATV6A0C31T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

Drive rating and fit

The ATV6A0C31T6 is a modular Altivar Process ATV600 drive rated for 350 hp at 600 V normal duty and 250 hp heavy duty. Line current draws 298 A (normal duty) or 218 A (heavy duty); apparent power is 310 kVA or 227 kVA respectively. Heavy-duty current of 218 A drives the high-overload rating for constant-torque loads; normal duty 298 A suits variable-torque centrifugal pumps and fans. Integrated EMC filter is rated for IEC 61800-3 Category C3 (industrial) with up to 300 m of motor cable, eliminating the need for an external filter in most plant-floor installations. Safe torque off (STO) function is SIL 3 compliant per IEC 61508, covering machine safety category requirements without external safety relays.

Communication and control options

Slot A accepts communication option cards for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen. Ethernet port runs 10/100 Mbit/s with half/full duplex autonegotiation. Onboard Modbus serial uses two-wire RS-485 at baud rates 4.8 to 38.4 kbit/s, RTU frame with configurable parity. Supports up to 247 addresses.

Protection and compliance

Listed protections include thermal and phase-loss for both motor and drive, overcurrent, short circuit, DC bus overvoltage, line supply over/undervoltage, and overspeed. STO is the primary safety function. Standards compliance includes IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61508 and IEC 13849-1 (functional safety), and UL 61800-5-1. Pollution degree 2 per IEC. Marking is CE. Rated for cabinet mount with UL Type 1 or Type 12 enclosure integration.

The modular version ships with the control unit, power module (200 kW), mounting kits, power connection set, fuses, and front cover. No additional base module required.

Frequently asked questions

What compliance documentation does the ATV6A0C31T6 carry?

It is CE marked and complies with IEC 61800-3, IEC 61800-5-1, IEC 61508, IEC 13849-1, and UL 61800-5-1.

What is the motor power rating?

350 hp at 600 V normal duty, 250 hp at 600 V heavy duty.

Does it support synchronous motors?

Yes, it is intended for both synchronous and asynchronous motors.

What fieldbus options are available?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen. Modbus serial is onboard.

MPN
ATV6A0C31T6