Skip to main content
Schneider Electric ATV6A0C50R4 — AC Drive (VFD) 480V

Schneider ATV6A0C50R4 Altivar Process, 500 kW 440 V AC drive

MPNATV6A0C50R4
Active

Schneider Altivar Process ATV600 modular drive, ATV6A0C50R4, 500 kW at 440 V normal duty, 400 kW heavy duty, integrated EMC filter C3, STO SIL 3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C50R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C50R4 — Power & Output
ParameterValue
Motor power (kW)500.0 kW at 440 V normal duty 400.0 kW at 440 V heavy duty
Continuous output current900.0 A at 2.5 kHz normal duty 730.0 A at 2.5 kHz heavy duty
Max. transient current990 A during 60 s (normal duty) 1095 A during 60 s (heavy duty)
Apparent power588 kVA at 440 V normal duty 475 kVA at 440 V heavy duty

Input / Supply

ATV6A0C50R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current771.0 A at 440 V (normal duty) 623.0 A at 440 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), <200 mA, protection type: overload and short-circuit protection

Control & Performance

ATV6A0C50R4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C50R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C50R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level71 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C50R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C50R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C50R4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The ATV6A0C50R4 is a modular Altivar Process ATV600 drive delivering 500 kW at 440 V in normal duty and 400 kW in heavy duty. Line current runs 771 A normal, 623 A heavy. The normal duty figure governs continuous constant-torque loads; heavy duty provides higher overload margin for cyclic or demanding applications. Integrated EMC filter meets IEC 61800-3 category C3 with 300 m of shielded cable, so many installations can skip an external filter. STO SIL 3 is built in — no option card needed for safe torque off. Standards compliance includes IEC 61800-3, -5-1, and 61000-3-12; CE marked.

Supply and I/O structure

External 24 V DC (19…30 V) powers the digital inputs. An internal supply provides 10.5 V ±5% for a reference potentiometer (1 to 10 kΩ), and a separate 24 V DC (21…27 V, <200 mA) for digital inputs and STO—with overload and short-circuit protection. Analog inputs AI1–AI3 are software-configurable for voltage (0…10 V, 30 kΩ) or current (0…20 mA/4…20 mA, 250 Ω), 12-bit resolution. DI5 and DI6 accept pulse inputs up to 30 kHz. Three relay outputs (R1–R3) are configurable for fault/sequence logic; R1 is NO/NC, R2 and R3 are NO. Electrical endurance rated 100,000 cycles.

Mounting and cooling

Cabinet mount with forced convection cooling. Pollution degree 2 per IEC 61800-5-1. Operating altitude up to 4800 m with 1% current derating per 100 m above 1000 m. Relative humidity 5–95% non-condensing. The modular variant ships as a kit: control unit, mounting hardware, power connection set, fuses, three 160 kW power modules, and two front covers.

Commissioning and connectivity

Slot A accepts communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen. Ethernet port supports half/full duplex and auto-negotiation. Serial port runs Modbus RTU at 4.8–38.4 kbps. Sampling for digital inputs is 2 ms, for analog inputs 5 ms—tight enough for most process loops.

Frequently asked questions

What is the difference between normal duty and heavy duty ratings?

Normal duty (500 kW, 771 A) is for continuous constant-torque loads. Heavy duty (400 kW, 623 A) provides higher overload capacity for applications like crushers or conveyors with peak torque demands.

Does the ATV6A0C50R4 include safe torque off?

Yes, it has built-in STO rated SIL 3 per IEC 61508 and IEC 13849-1—no optional safety module required.

What integrated EMC filter does this drive have?

It includes a filter compliant with IEC 61800-3 category C3 for 300 m of shielded cable, suitable for most industrial environments without an external filter.

MPN
ATV6A0C50R4