Skip to main content
Schneider Electric ATV6A0C71Q4 — AC Drive (VFD) 480V

Schneider ATV6A0C71Q4 Altivar Process Drive, 710 kW

MPNATV6A0C71Q4
Active

Schneider Electric Altivar Process ATV600, modular drive, ATV6A0C71Q4, 710 kW normal duty / 560 kW heavy duty at 400 V, 1192 A line current, with integrated EMC filter, STO SIL3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6A0C71Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6A0
Product range / familyAltivar Process ATV600

Power & Output

ATV6A0C71Q4 — Power & Output
ParameterValue
Motor power (kW)710.0 kW at 400 V normal duty 560.0 kW at 400 V heavy duty
Continuous output current1260.0 A at 2.5 kHz normal duty 1020.0 A at 2.5 kHz heavy duty
Max. transient current1386 A during 60 s (normal duty) 1530 A during 60 s (heavy duty)
Apparent power826 kVA at 400 V normal duty 659 kVA at 400 V heavy duty

Input / Supply

ATV6A0C71Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current1192.0 A at 400 V (normal duty) 951.0 A at 400 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), <200 mA, protection type: overload and short-circuit protection

Control & Performance

ATV6A0C71Q4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor

Protection & EMC

ATV6A0C71Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6A0C71Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level74 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6A0C71Q4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6A0C71Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6A0C71Q4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The ATV6A0C71Q4: Sized for a 710 kW induction motor on 400 V three-phase under normal duty; the heavy-duty rating steps down to 560 kW. Line current of 1192 A ND or 951 A HD sets the upstream breaker and cable class. Internal supply for digital inputs and STO is 24 V DC (21...27 V) at under 200 mA with overload protection; an external 24 V DC (19...30 V) supply feeds the discrete inputs if the internal rail is not used. The integrated EMC filter meets IEC 61800-3 Category C3 for up to 300 m of motor cable, which keeps the cabinet clean on most standard installations. Safe torque off (STO) functional safety is built in at SIL 3 per IEC 61508 – no separate safety module needed for the stop circuit on machinery that requires it.

Cabinet-mounted, forced convection cooled. Pollution degree 2 per IEC 61800-5-1. Shock resistance rated at 7 gn for 11 ms. Relative humidity 5 to 95 % non-condensing. Ambient temperature range is not explicitly listed, but the storage and handling limits are typically wider than operating range – the integrated fan and heatsink assume a clean airflow path.

Frequently asked questions

What is the supply requirement for digital inputs and STO?

The drive provides an internal 24 V DC supply (21...27 V) for digital inputs and safe torque off, rated at under 200 mA with overload and short-circuit protection. An external 24 V DC supply (19...30 V) can also be used for the digital inputs.

What compliance markings does this drive carry?

It carries CE marking and conforms to IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

What is the motor power rating at 400 V?

710 kW for normal duty and 560 kW for heavy duty at 400 V, with corresponding line currents of 1192 A and 951 A.

MPN