Skip to main content
Schneider Electric ATV6A0M12T6 — AC Drive (VFD) 600V

ATV6A0M12T6 Altivar Process ATV600, 1200 HP at 600 V

MPNATV6A0M12T6
Active

Schneider Electric Altivar Process ATV600, ATV6A0M12T6, modular variable speed drive, 1200 hp at 600 V normal duty, 994 A line current, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6A0M12T6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6A0
Product / component typeVariable speed drive
ATV6A0M12T6 — Electrical (input)
ParameterValue
Rated supply voltage600 V - 15...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current994.0 A 600 V normal duty) 835.0 A 600 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<48 % full load IEC 61000-3-12
ATV6A0M12T6 — Output / Performance
ParameterValue
Apparent power1033 kVA at 600 V normal duty 868 kVA at 600 V heavy duty
Continuous output current1230.0 A at 2.5 kHz normal duty 1030.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6A0M12T6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6A0M12T6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6A0M12T6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level75 dB 86/188/EEC
ATV6A0M12T6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 UL 61800-5-1
Agency markings / approvalsCE

Product details

Commissioning note

This ATV6A0M12T6 is a modular Altivar Process ATV600 drive sized for a 1200 hp motor at 600 V normal duty (1000 hp heavy duty), pulling 994 A line current normal and 835 A heavy. The integrated EMC filter meets Category C3 for cable runs up to 300 m, saving an external filter cabinet. Communication stack includes dual Ethernet ports (Modbus TCP) and a 2-wire RS-485 for Modbus serial RTU. The slot-A option bay accepts Profibus DP V1, PROFINET, DeviceNet, CANopen, or Ethernet/IP; slot A/B also take digital/analog I/O or relay expansion. Safe torque off is SIL 3 rated. On the supply side, it operates from 50/60 Hz, adjustable switching frequency from 2 to 4.9 kHz with derating, and prospective line short-circuit current rated for 50 kA. Compliance includes IEC 61800-3, 61800-5-1, UL 61800-5-1, and pollution degree 2.

No last-time-buy or phase-out applies.

Cabinet integration

Cabinet mount. Power connections: line side screw terminal, motor M10 x 2 bars. Control wiring via removable screw terminals accepting 0.5–1.5 mm² (AWG 20–16). Vibration resistance: 1.5 mm peak-to-peak at 2–13 Hz, 0.5 gn at 13–200 Hz (IEC 60068-2-6). Shock 4 gn for 11 ms (IEC 60068-2-27). Humidity range 5–95% non-condensing (IEC 60068-2-3). Forced convection cooling; ensure clearances per manual for airflow.

Frequently asked questions

What is the ATV6A0M12T6's CE marking?

The drive carries CE marking, confirming conformity with EU directives.

What is the ATV6A0M12T6's variant?

It is a modular version, delivered as a kit with control unit, power module, mounting kit, wiring set, fuses, and front cover.

What compliance documentation does the ATV6A0M12T6 come with?

It complies with IEC 61800-3, IEC 61800-5-1, UL 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. Documentation is provided per standard practices.

MPN
ATV6A0M12T6