Schneider Electric ATV6B0C13Q4 — AC Drive (VFD) 480V

Schneider ATV6B0C13Q4 Altivar Process ATV600, 132 kW normal

MPNATV6B0C13Q4
Active

Schneider Electric Altivar Process ATV600, modular VFD, ATV6B0C13Q4, 132 kW normal duty / 110 kW heavy duty at 400 V, 208 A line current, STO SIL 3, integrated EMC C3 filter.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C13Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C13Q4 — Power & Output
ParameterValue
Motor power (kW)132.0 kW at 400 V normal duty 110.0 kW at 400 V heavy duty
Continuous output current250.0 A at 2.5 kHz normal duty 211.0 A at 2.5 kHz heavy duty
Max. transient current275 A during 60 s (normal duty) 316.5 A during 60 s (heavy duty)
Apparent power144 kVA at 400 V normal duty 121 kVA at 400 V heavy duty

Input / Supply

ATV6B0C13Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current208.0 A at 400 V (normal duty) 174.0 A at 400 V (heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C13Q4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C13Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C13Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level70 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C13Q4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C13Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C13Q4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

Drive selection memo — ATV6B0C13Q4

Schneider's ATV6B0C13Q4 is a modular Altivar Process ATV600 drive rated for 132 kW normal duty and 110 kW heavy duty at 400 V, drawing 208 A line current in normal duty and 174 A in heavy duty. It ships as a kit: power module, control unit, mounting hardware, power connection set, and a set of fuses — no separate ordering of accessories for a basic install. Built for both asynchronous and synchronous motors, with an adjustable switching frequency from 2 to 8 kHz (derate above 2.5 kHz). The integrated EMC filter meets IEC 61800-3 category C3 for 300 m cable runs, so you can skip an external filter for most industrial line-ups. Pollution degree 2, vibration and shock per IEC 60068-2-6 and 60068-2-27.

Fieldbus and I/O — slot architecture

Slot A accepts a communication module for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D 9, or screw terminals). Slot A and slot B can each take a digital/analog I/O extension or an output relay extension. The base unit includes a slave Modbus TCP port (10/100 Mbit/s) and a 2-wire RS 485 Modbus serial port (4.8 to 38.4 kbit/s, RTU frame, 1–247 addresses). Control wiring lands on removable screw terminals accepting 0.5–1.5 mm² (AWG 20–16). Line-side connection is screw terminal; motor connection uses M10 x 2 bars.

This is a current-production item — no end-of-life notice on file. It carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1. The integrated EMC filter is C3 rated for 300 m cable, and total harmonic current distortion (THDI) stays under 5% at full load per IEEE 519. Operating altitude is 1000 m base with derating up to 4800 m. Ambient relative humidity 5–95% non-condensing. Power dissipation at 2.5 kHz switching: 5040 W normal duty, 4180 W heavy duty — plan cabinet cooling accordingly.

Frequently asked questions

What are the key ratings for ATV6B0C13Q4?

132 kW normal duty / 110 kW heavy duty at 400 V, 208 A line current normal duty, 174 A heavy duty, STO SIL 3 safety function, integrated EMC C3 filter for 300 m cable.

What fieldbus options does this drive support?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen modules. Base unit includes slave Modbus TCP and RS 485 Modbus serial.

What compliance documentation is available?

CE marking, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1, and IEEE 519 for THDI <5%.

MPN
ATV6B0C13Q4