Schneider Electric ATV6B0C16Q6 — AC Drive (VFD) 600V

Schneider ATV6B0C16Q6 ATV600 Drive, 160kW 690V

MPNATV6B0C16Q6
Active

Schneider Altivar Process ATV600, modular version, ATV6B0C16Q6, 160 kW at 690 V heavy duty, integrated EMC filter C3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C16Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6B0
Product / component typeVariable speed drive

Electrical (input)

ATV6B0C16Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 10...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current148.0 A 690 V normal duty) 122.0 A 690 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519

Output / Performance

ATV6B0C16Q6 — Output / Performance
ParameterValue
Apparent power177 kVA at 690 V normal duty 146 kVA at 690 V heavy duty
Continuous output current175.0 A at 2.5 kHz normal duty 145.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor

Communication

ATV6B0C16Q6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial

Mechanical

ATV6B0C16Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors

Environmental

ATV6B0C16Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level70 dB 86/188/EEC

Approvals & Compliance

ATV6B0C16Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

The Schneider ATV6B0C16Q6 is a modular variable speed drive from the Altivar Process ATV600 series, sized for 160 kW at 690 V in heavy-duty motor duty and 122 A line current under the same condition — that's your load-fit anchor when commissioning a 690 V induction or synchronous motor. The integrated EMC filter meets IEC 61800-3 category C3 for industrial environments, so you can skip an external filter in most panel builds. Safe torque off (STO) at SIL 3 is built in, eliminating the need for a separate safety relay for that function.

Cabinet-mount only, forced convection cooling — ensure clearance for airflow. Pollution degree 2 environment expected. Electrical connections: line side via screw terminals, motor side via M10 bus bars (torque to manufacturer spec). Slot A accepts communication option cards for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D, or screw terminals); slot A/B can host digital/analog I/O or relay extension modules. Commissioning engineer tip: the switching frequency is adjustable from 2 to 4.9 kHz with a derating factor, and the integrated EMC filter covers up to 300 m of motor cable at C3 level.

Frequently asked questions

What are its CE marking and key standards?

The drive carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

What is the maximum motor power at 690 V heavy duty?

Rated 132 kW heavy duty and 160 kW normal duty at 690 V, with corresponding line currents of 122 A and 148 A.

Does it include safe torque off?

Yes, STO (safe torque off) at SIL 3 is integrated into the drive.

MPN