Schneider Electric ATV6B0C25Q6 — AC Drive (VFD) 600V

Schneider ATV6B0C25Q6 Altivar Process Drive, 250 kW

MPNATV6B0C25Q6
Active

Schneider Electric Altivar Process ATV600 ATV6B0C25Q6 modular drive, 250 kW normal duty / 200 kW heavy duty at 690 V, with integrated EMC filter and STO SIL3.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C25Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6B0
Product / component typeVariable speed drive

Electrical (input)

ATV6B0C25Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 10...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current228.0 A 690 V normal duty) 183.0 A 690 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519

Output / Performance

ATV6B0C25Q6 — Output / Performance
ParameterValue
Apparent power273 kVA at 690 V normal duty 219 kVA at 690 V heavy duty
Continuous output current275.0 A at 2.5 kHz normal duty 215.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor

Communication

ATV6B0C25Q6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial

Mechanical

ATV6B0C25Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors

Environmental

ATV6B0C25Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level73 dB 86/188/EEC

Approvals & Compliance

ATV6B0C25Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

The Schneider ATV6B0C25Q6 is a modular variable speed drive from the Altivar Process ATV600 range, rated for 250 kW normal duty at 690 V and 200 kW heavy duty, with a corresponding line current of 228 A normal / 183 A heavy. It carries an integrated EMC filter compliant with IEC 61800-3 category C3, covering up to 300 m of motor cable, and offers Safe Torque Off (STO) to SIL 3.

The integrated EMC filter (category C3) is sized for industrial environments where the drive is installed in a cabinet with a protective earth. It suppresses both conducted and radiated emissions on the line and motor sides, which saves you an external filter in most second-environment applications. That means the drive can serve in safety-related control loops without a separate safety relay, as long as your control system handles the dual-channel request. Forced-convection cooling means fan noise is present — 73 dB per the EEC directive — so plan the cabinet ventilation accordingly if noise is a constraint in the machine cell.

Fieldbus and I/O options

Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen (with three connector variants). Slot A/B also takes digital/analog I/O extensions or a relay output module. The drive ships with a Modbus serial port (2-wire RS-485, RTU, 4.8–38.4 kbit/s) and a Modbus TCP port (10/100 Mbit/s half/full duplex) as standard. This gives you a flexible fieldbus interface without opening the box for an optional card in many cases.

Cabinet mount only (UL type 1 or 12 when integrated); pollution degree 2; operating altitude ≤2000 m with derating above 1000 m; shock 4 gn/11 ms; vibration 1.5 mm peak-peak at 2–13 Hz and 0.5 gn at 13–200 Hz. Forced convection requires clearance for airflow.

Frequently asked questions

Is the ATV6B0C25Q6 CE marked?

Yes, Marking CE is listed on the product.

What motor types does this drive support?

It is designed for synchronous and asynchronous motors.

What safety functions are integrated?

Safe Torque Off (STO) to SIL 3 per IEC 61508 and IEC 13849-1 is standard.

Does it come with an integrated EMC filter?

Yes, an integrated EMC filter compliant with IEC 61800-3 category C3, rated for 300 m of motor cable.

What communication ports are standard?

Standard ports include a 2-wire RS-485 Modbus serial (RTU, 4.8–38.4 kbit/s) and a Modbus TCP port (10/100 Mbit/s).

MPN