Skip to main content
Schneider Electric ATV6B0C45Q4 — AC Drive (VFD) 480V

Schneider ATV6B0C45Q4 Altivar Process Drive, 450kW

MPNATV6B0C45Q4
Active

Schneider Electric Altivar Process ATV600 series, ATV6B0C45Q4, VFD, modular version, 450 kW normal duty at 400 V, integrated EMC filter C3, STO SIL3, cabinet mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C45Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C45Q4 — Power & Output
ParameterValue
Motor power (kW)450.0 kW at 400 V normal duty 355.0 kW at 400 V heavy duty
Continuous output current830.0 A at 2.5 kHz normal duty 660.0 A at 2.5 kHz heavy duty
Max. transient current913 A during 60 s (normal duty) 990 A during 60 s (heavy duty)
Apparent power483 kVA at 400 V normal duty 383 kVA at 400 V heavy duty

Input / Supply

ATV6B0C45Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current697.0 A at 400 V (normal duty) 553.0 A at 400 V (heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C45Q4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C45Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C45Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level75 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C45Q4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C45Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C45Q4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

ATV6B0C45Q4 is a 450 kW Altivar Process ATV600 drive for asynchronous or synchronous motors on 400 V three-phase supply. Its integrated EMC filter (category C3) covers 300 m motor cable runs, eliminating an external filter box for most installations. Rated 697 A line current at normal duty and 553 A at heavy duty. STO SIL3 is built into the control board — no separate safety relay needed for torque-off.

Cabinet mount, forced-convection cooled. Electrical connection uses M10 bars on the motor side, screw terminals for control (0.5…1.5 mm²). Slot A accepts communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (with various physical interfaces). Slot A/B also accept digital/analog I/O or output relay extensions. Modbus serial (RS-485 2-wire) is native, configurable for 8 bits, odd/even/no parity.

Key ratings so-what

Line current 697 A (normal duty) sets the supply conductor and fuse sizing; heavy duty at 553 A gives headroom for overload profiles. Switching frequency adjustable 2…8 kHz; 18690 W dissipated at 2.5 kHz normal duty drives cooling requirements. Prospective line Isc rated 50 kA — suitable for high-fault-capacity installations.

Frequently asked questions

What is the marking and variant of this unit?

Marking is CE. The variant is listed as 'Modular version', meaning it is part of the modular Altivar Process family with slot-based expansion.

What communication protocols are supported?

The drive includes native Modbus serial (RS-485, RTU) and Modbus TCP. Slot A can accept optional modules for Profibus DP V1, PROFINET, DeviceNet, EtherNet/IP, or CANopen.

MPN
ATV6B0C45Q4