Skip to main content
Schneider Electric ATV6B0C50R4 — AC Drive (VFD) 480V

Schneider ATV6B0C50R4 Altivar Process Drive, 500 kW

MPNATV6B0C50R4
Active

Schneider Electric Altivar Process ATV600, ATV6B0C50R4, 500 kW normal duty at 440 V, integrated EMC filter C3, STO SIL 3, modular version.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C50R4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C50R4 — Power & Output
ParameterValue
Motor power (kW)500.0 kW at 440 V normal duty 400.0 kW at 440 V heavy duty
Continuous output current900.0 A at 2.5 kHz normal duty 730.0 A at 2.5 kHz heavy duty
Max. transient current990 A during 60 s (normal duty) 1095 A during 60 s (heavy duty)
Apparent power537 kVA at 440 V normal duty 429 kVA at 440 V heavy duty

Input / Supply

ATV6B0C50R4 — Input / Supply
ParameterValue
Rated supply voltage range440 V - 15...10 %
Input line current704.0 A at 440 V (normal duty) 563.0 A at 440 V (heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C50R4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C50R4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C50R4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level75 dB conforming to 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C50R4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C50R4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C50R4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

Where this drive is typically applied

The ATV6B0C50R4 is used to control synchronous and asynchronous motors in industrial process applications — pumping, conveying, fan arrays, and extruders where power quality and safety integration matter. The modular version separates the power module and control unit (the kit includes a 160 kW power module and a separate control unit), so a failed power stack can be swapped without touching control wiring, and vice versa. Standard cabinet-mount frame with M10 busbar connections on the motor side and screw terminals for control wiring up to 1.5 mm².

Fieldbus and communication options

Slot A accepts communication modules for PROFIBUS DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (with daisy-chain RJ45, SUB-D 9, or screw terminals). Both Slot A and Slot B accept digital/analog I/O extension or output relay extension modules. The drive ships with Modbus serial (RS-485, 2-wire) and Modbus TCP/Ethernet (10/100 Mbit/s) as standard, so you can commission it on the built-in protocols immediately.

Frequently asked questions

What compliance documentation does this drive carry?

It carries CE marking and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and ISO 13849-1. Specific declarations and certificates are supplied with the unit or upon request.

What does the 'Modular version' variant mean for service?

Modular version means the power module and control unit are separate assemblies. The kit composition includes one control unit and a 160 kW power module, so a field swap of either section is possible without disturbing the other, reducing repair time.

MPN
ATV6B0C50R4