Schneider Electric ATV6B0C56T4 — AC Drive (VFD) 480V

ATV6B0C56T4 Altivar Process ATV600, 800 hp, 480 V

MPNATV6B0C56T4
Active

Schneider Electric Altivar Process ATV600, ATV6B0C56T4, modular VFD, 800 hp at 480 V normal duty, 560 kW, 771 A line current, cabinet mount.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ATV6B0C56T4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600

Power & Output

ATV6B0C56T4 — Power & Output
ParameterValue
Motor power (kW)560.0 kW at 480 V normal duty 450.0 kW at 480 V heavy duty
Continuous output current1020.0 A at 2.5 kHz normal duty 830.0 A at 2.5 kHz heavy duty
Max. transient current1122 A 60 s normal duty) 1245 A 60 s heavy duty)
Apparent power641 kVA at 480 V normal duty 520 kVA at 480 V heavy duty

Input / Supply

ATV6B0C56T4 — Input / Supply
ParameterValue
Rated supply voltage range480 V - 10...10 %
Input line current771.0 A 480 V normal duty) 626.0 A 480 V heavy duty)
Network number of phases3 phases

Control & Performance

ATV6B0C56T4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor

Protection & EMC

ATV6B0C56T4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Protection functionsThermal protection motor Safe torque off motor Motor phase break motor Thermal protection drive Safe torque off drive Overheating drive Overcurrent between output phases and earth drive Overload of output voltage drive Short-circuit protection drive Motor phase break drive Overvoltages on the DC bus drive Line supply overvoltage drive Line supply undervoltage drive Line supply phase loss drive Overspeed drive Break on the control circuit drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA

Mechanical & Cooling

ATV6B0C56T4 — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP degree of protectionIP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Acoustic noise level77 dB 86/188/EEC
Cooling methodForced convection

Environmental

ATV6B0C56T4 — Environmental
ParameterValue
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Operating altitude1000...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2 IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6

Approvals

ATV6B0C56T4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1

Communication

ATV6B0C56T4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

Modular high-power drive for process applications

ATV6B0C56T4 is the modular version of the Altivar Process ATV600 family—a cabinet-mount drive module rated 800 hp (560 kW) at 480 V normal duty, 650 hp (450 kW) heavy duty. Line current pulls 771 A at normal duty, 626 A under heavy duty. Designed for synchronous and asynchronous motors, with DC injection braking and an adjustable switching frequency of 2.5 to 8 kHz (derated above 2 kHz). Modular version means the kit includes the control unit, power module, mechanical mounting kit, power connections, and a set of fuses—you supply the enclosure and integrate per the cabinet mount instructions. Communication is handled via the built-in Modbus serial (RTU, 2-wire RS485, 1–247 addresses) and a dual Ethernet port supporting Modbus TCP/IP at 10/100 Mbit/s. Slot A accepts optional Profibus DP V1, PROFINET, DeviceNet, CANopen, or I/O extension cards.

Compliance and safety planning

Integrated EMC filter meets IEC 61800-3 category C3 for 984.3 ft (300 m) cable. Prospective line short-circuit current rated 50 kA. Pollution degree 2 per IEC 61800-5-1, 5–95% non-condensing humidity, and operation up to 4800 m with derating above 1000 m.

Frequently asked questions

What is ATV6B0C56T4's listed marking (CE) on this component line?

CE marking is listed.

What is ATV6B0C56T4's listed variant?

Modular version for cabinet integration.

What compliance documentation does this brand provide for ATV6B0C56T4 (RoHS, REACH, UL, IEC)?

The drive meets IEC 61800-3, IEC 61800-5-1, IEC 61508 SIL 3 for safety, and UL 61800-5-1 (UL type 1/12 when cabinet integrated).

MPN