Drive rating and motor fit
The Schneider Electric ATV6B0C80N6 is a modular Altivar Process ATV600 drive rated for 560 kW at 500 V normal duty and 450 kW at 500 V heavy duty, covering asynchronous and synchronous motors. The integrated EMC filter meets IEC 61800-3 category C3, allowing up to 300 m of shielded cable without external filtering. Line current pulls 701 A at 500 V normal duty, 564 A at 500 V heavy duty. Prospective line Isc rating is 50 kA, so coordination with upstream protection is straightforward.
Communication and control options
Slot A accepts plug-in communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D 9, or screw terminals). Slot A and slot B also accept digital/analog I/O extension and output relay modules. Built-in Modbus serial is 2-wire RS-485, RTU mode, 8-bit configurable parity, addresses 1–247. Ethernet runs 10/100 Mbit/s with half/full duplex autonegotiation.
Safety and protection features
Safe torque off (STO) is rated SIL 3 per IEC 61508. Protection covers motor and drive thermal, output phase/earth faults, line undervoltage/overvoltage/phase loss, overspeed, and DC bus overvoltage. Braking to standstill is by DC injection.
Cabinet mount, forced convection cooling. Vibration resistance to IEC 60068-2-6: 1.5 mm peak-peak at 2–13 Hz, 0.5 gn at 13–200 Hz. Shock: 4 gn for 11 ms. Altitude up to 2000 m with derating above 1000 m. Relative humidity 5–95% non-condensing.