Skip to main content
Schneider Electric ATV6B0M10Q4 — AC Drive (VFD) 480V

Schneider Electric ATV6B0M10Q4 Altivar Process Drive, 1000 k

MPNATV6B0M10Q4
Active

Schneider Electric Altivar Process ATV600, ATV6B0M10Q4, modular drive, 1000 kW normal duty / 800 kW heavy duty at 400 V, forced convection cooling, cabinet mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

ATV6B0M10Q4 — Identification
ParameterValue
Product typeVariable speed drive
Device short nameATV6B0
Product range / familyAltivar Process ATV600
ATV6B0M10Q4 — Power & Output
ParameterValue
Motor power (kW)1000.0 kW at 400 V normal duty 800.0 kW at 400 V heavy duty
Continuous output current1770.0 A at 2.5 kHz normal duty 1420.0 A at 2.5 kHz heavy duty
Max. transient current1947 A during 60 s (normal duty) 2130 A during 60 s (heavy duty)
Apparent power1074 kVA at 400 V normal duty 859 kVA at 400 V heavy duty
ATV6B0M10Q4 — Input / Supply
ParameterValue
Rated supply voltage range400 V - 15...10 %
Input line current1550.0 A at 400 V (normal duty) 1240.0 A at 400 V (heavy duty)
Network number of phases3 phases
Internal/auxiliary suppliesExternal supply for digital inputs: 24 V DC (19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO: 24 V DC (21...27 V), <200 mA, protection type: overload and short-circuit protection
ATV6B0M10Q4 — Control & Performance
ParameterValue
Output frequency range0...500 Hz
Asynchronous motor control modesConstant torque standard Variable torque standard Optimized torque mode
Synchronous motor control modesPermanent magnet motor Synchronous reluctance motor
ATV6B0M10Q4 — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated with 300 m conforming to IEC 61800-3 category C3
Protection functionsThermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Prospective short-circuit current (Isc)50 kA
ATV6B0M10Q4 — Mechanical & Cooling
ParameterValue
IP degree of protectionIP00 (for IP21 or IP54 cabinet integration) conforming to IEC 61800-5-1 IP00 (for IP21 or IP54 cabinet integration) conforming to IEC 60529
Acoustic noise level79 dB conforming to 86/188/EEC
Cooling methodForced convection
ATV6B0M10Q4 — Environmental
ParameterValue
Operating ambient temperature-10...40 °C without derating 40...50 °C with derating factor
Operating altitude0...4800 m with current derating above 1000m
Relative humidity5...95 % without condensation conforming to IEC 60068-2-3
Storage / transport temperature-40...70 °C
Pollution degree2 conforming to IEC 61800-5-1
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV6B0M10Q4 — Approvals
ParameterValue
Certifications & markingCE
Standards complianceIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATV6B0M10Q4 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP

Product details

The ATV6B0M10Q4 is a modular Altivar Process ATV600 drive rated for 1000 kW motor power at 400 V in normal duty, 800 kW in heavy duty operation. It draws 1550 A line current (normal duty) and 1240 A (heavy duty). Integrated EMC filter meets IEC 61800-3 Category C3 with 300 m cable. Safety function STO SIL 3 is included. Supplies for digital inputs and STO are onboard: external 24 V DC (19...30 V) for digital inputs, internal 24 V DC (21...27 V) for STO, and an internal 10.5 V DC reference for a potentiometer (1 to 10 kΩ).

Field connections and options

Cabinet mount, forced convection cooling. Slot A accepts communication modules: Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, CANopen (daisy chain RJ45, SUB-D 9, screw terminals). Slots A and B accept digital/analog I/O extension and output relay extension modules. Embedded Modbus serial RS-485 at 4.8–38.4 kbps, RTU. Ethernet/IP and Modbus TCP at 10/100 Mbps. Analog inputs (3): software-configurable voltage 0–10 V DC or current 0/4–20 mA, 12-bit, linearity ±0.15%. Digital inputs (6): 24 V DC, two configurable as pulse inputs (0–30 kHz). Relay outputs: R1 fault NO/NC, R2 and R3 sequence NO, each rated for 100,000 cycles.

Frequently asked questions

What are the key ratings for the ATV6B0M10Q4?

Motor power is 1000 kW at 400 V normal duty and 800 kW at 400 V heavy duty. Line current is 1550 A (normal duty) and 1240 A (heavy duty).

What supply voltages does the ATV6B0M10Q4 require?

It requires an external 24 V DC supply (19...30 V) for digital inputs, internal 24 V DC (21...27 V) for digital inputs and STO, and provides an internal 10.5 V DC reference for a potentiometer (1 to 10 kΩ).

What compliance standards does the ATV6B0M10Q4 meet?

It is CE marked and complies with IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, and IEC 13849-1.

What communication options are available for the ATV6B0M10Q4?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, and CANopen modules. Embedded communications include Modbus serial RS-485 and Ethernet IP/Modbus TCP.

MPN
ATV6B0M10Q4