Skip to main content
Schneider Electric ATV6B0M12Q6 — AC Drive (VFD) 600V

Schneider ATV6B0M12Q6 Altivar Process ATV600 Drive, 1200 kW

MPNATV6B0M12Q6
Active

Schneider Electric Altivar Process ATV600, modular VFD, ATV6B0M12Q6, 1200 kW at 690 V normal duty, 1078 A line current, STO SIL 3, integrated EMC filter C3.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ATV6B0M12Q6 — Identification
ParameterValue
Product range / seriesAltivar Process ATV600
Device short name / model codeATV6B0
Product / component typeVariable speed drive
ATV6B0M12Q6 — Electrical (input)
ParameterValue
Rated supply voltage690 V - 10...10 %
Network phases3 phases
Supply frequency50...60 Hz - 5...5 %
Line (input) current1078.0 A 690 V normal duty) 898.0 A 690 V heavy duty)
Prospective line short-circuit current (Isc)50 kA
EMC filterIntegrated 984.3 ft (300 m) IEC 61800-3 category C3
Max. input current THD (THDi)<5 % full load IEEE 519
ATV6B0M12Q6 — Output / Performance
ParameterValue
Apparent power1288 kVA at 690 V normal duty 1073 kVA at 690 V heavy duty
Continuous output current1230.0 A at 2.5 kHz normal duty 1030.0 A at 2.5 kHz heavy duty
Switching (PWM) frequency2...4.9 kHz adjustable with derating factor
ATV6B0M12Q6 — Communication
ParameterValue
Communication protocolsEthernet Modbus serial Modbus TCP
Address range1...247 Modbus serial
Data format8 bits, configurable odd, even or no parity Modbus serial
ATV6B0M12Q6 — Mechanical
ParameterValue
Mounting modeCabinet mount
Terminal / wiring connectionControl removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 Line side screw terminal Motor M10 x 2 bars
Product destination / compatibilitySynchronous motors Asynchronous motors
ATV6B0M12Q6 — Environmental
ParameterValue
Degree of protection (IEC, IP)UL type 1 conforming to UL 61800-5-1 (cabinet integration) UL type 12 conforming to UL 61800-5-1 (cabinet integration)
IP rating (with kit options)IP00 for IP21 or IP54 cabinet integration)IEC 61800-5-1 IP00 for IP21 or IP54 cabinet integration)IEC 60529
Operating ambient temperature14...104 °F (-10...40 °C) without derating 104...122 °F (40...50 °C) with derating factor
Storage temperature-40...158 °F (-40...70 °C)
Operating altitude (with derating)< 2000 m with current derating above 1000m
Relative humidity5...95 % without condensation IEC 60068-2-3
Pollution degree2 IEC 61800-5-1
Environmental resistance classesChemical pollution resistance class 3C3 IEC 60721-3-3 Dust pollution resistance class 3S3 IEC 60721-3-3 Humidity resistant class 3K3 IEC 60721-3-3
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 0.5 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
Shock resistance4 gn 11 ms IEC 60068-2-27
Acoustic noise level79 dB 86/188/EEC
ATV6B0M12Q6 — Approvals & Compliance
ParameterValue
StandardsIEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
Agency markings / approvalsCE

Product details

Drive selection memo: ATV6B0M12Q6

The ATV6B0M12Q6 is a modular Altivar Process ATV600 drive rated for 1200 kW at 690 V normal duty and 1000 kW at 690 V heavy duty, drawing 1078 A line current normal duty and 898 A heavy duty. Apparent power comes to 1288 kVA normal duty, 1073 kVA heavy duty. It drives both synchronous and asynchronous motors, with a switching frequency adjustable from 2 to 4.9 kHz subject to derating. The integrated EMC filter meets IEC 61800-3 category C3 for motor cable runs up to 300 m. Lifecycle is active. The drive carries CE marking and complies with IEC 61800-3, 61800-5-1, 61000-3-12, 60721-3, 61508, and 13849-1. STO (safe torque off) is integrated at SIL 3.

Fieldbus slice and safety CPU separation

Slot A accepts communication modules for Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen (RJ45, SUB-D 9, or screw terminals). Slot A/B also accepts digital/analog I/O extension and output relay extension modules. The native Modbus serial interface is 2-wire RS485, RTU frame, 8-bit data with configurable parity, addresses 1–247, at 4.8–38.4 kbit/s. The Ethernet port runs Modbus TCP at 10/100 Mbit/s with half/full duplex and autonegotiation, slave access. For safety CPU separation, the STO function is built into the drive and does not require an external safety relay for SIL 3 applications. The protection suite covers thermal, motor phase break, overcurrent between output phases and earth, overload, short-circuit, overvoltage/undervoltage on the DC bus and line supply, line supply phase loss, overspeed, and break on the control circuit.

SCCR headroom and coordination

Prospective line short-circuit current rating is 50 kA, which gives headroom for high-fault installations. The drive is cabinet-mount only, with UL Type 1 and Type 12 enclosure ratings per UL 61800-5-1 for cabinet integration. Forced convection cooling handles the thermal load; the operating altitude is below 2000 m with derating above 1000 m. Pollution degree 2 per IEC 61800-5-1. THDI stays under 5% at full load per IEEE 519, which simplifies harmonic filter selection upstream. The supply frequency range is 50–60 Hz ±5%.

Kit composition and wiring

The kit includes one control unit, mechanical mounting kits, power connection set, fuses (6.0), power module 200 kW, and front cover. Electrical connection uses control removable screw terminals 0.5–1.5 mm² (AWG 20–16), line side screw terminal, and motor M10 x 2 bars. Braking to standstill is by DC injection.

Frequently asked questions

What are the key power ratings of the ATV6B0M12Q6?

Motor power is 1200 kW at 690 V normal duty and 1000 kW at 690 V heavy duty. Line current is 1078 A normal duty and 898 A heavy duty. Apparent power is 1288 kVA normal duty and 1073 kVA heavy duty.

What safety functions does the ATV6B0M12Q6 include?

Safe torque off (STO) is integrated at SIL 3. Additional protections cover thermal, motor phase break, overcurrent, overload, short-circuit, overvoltage/undervoltage, line supply phase loss, overspeed, and control circuit break.

What communication options are available for the ATV6B0M12Q6?

Slot A accepts Profibus DP V1, PROFINET, DeviceNet, Modbus TCP/EtherNet/IP, or CANopen modules. Native Modbus serial is 2-wire RS485 RTU at 4.8–38.4 kbit/s. Ethernet supports Modbus TCP at 10/100 Mbit/s.

MPN