Specifications

ATV930C16N4CUS — Identification
ParameterValue
Product typeVariable speed drive
Product range / familyAltivar Process ATV900
ATV930C16N4CUS — Power & Output
ParameterValue
Motor power (kW)160.0 kW normal duty 132.0 kW heavy duty
Continuous output current302 A 2.5 kHz normal duty 250 A 2.5 kHz heavy duty
ATV930C16N4CUS — Input / Supply
ParameterValue
Rated supply voltage range380...480 V
Internal/auxiliary suppliesExternal supply for digital inputs 24 V DC 19...30 V), Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, Internal supply for digital inputs and STO 24 V DC 21...27 V), 1 MOhm 500 V DC for 1 minute to earth
ATV930C16N4CUS — Protection & EMC
ParameterValue
Integrated EMC filter classIntegrated With EMC plate option
EMC immunity testsElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
ATV930C16N4CUS — Mechanical & Cooling
ParameterValue
Degree of protection (IP)UL type 1
IP degree of protectionIP21
Acoustic noise level69.9 dB
Assembly / installation styleEnclosed
ATV930C16N4CUS — Environmental
ParameterValue
Operating ambient temperature5...122 °F (-15...50 °C) (without derating) 122...140 °F (50...60 °C) (with derating factor)
Operating altitude1000...4800 m with current derating 1 % per 100 m
Relative humidity5...95 % without condensation IEC 60068-2-3
Storage / transport temperature-40...158 °F (-40...70 °C)
Pollution degree2
Vibration resistance1.5 mm peak to peak (f= 2...13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13...200 Hz) conforming to IEC 60068-2-6
ATV930C16N4CUS — Approvals
ParameterValue
Certifications & markingCE
Standards complianceUL 508C IEC 61800-3 IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1
ATV930C16N4CUS — Communication
ParameterValue
Communication protocolsModbus serial Modbus TCP EtherNet/IP

Product details

This ATV930C16N4CUS is a variable speed drive from the Altivar Process ATV900 family, designed for 3-phase asynchronous and synchronous motors. It delivers 160 kW normal duty or 132 kW heavy duty from a 380-480 V supply, with a continuous output current of 302 A at 2.5 kHz for normal duty.

Control supply and I/O wiring

Control wiring runs on an external 24 V DC supply for digital inputs (19-30 V range). Separate internal supplies provide 10.5 V DC for a reference potentiometer (1-10 kΩ) and 24 V DC (21-27 V) for digital inputs and the STO safety function. The drive passes a 500 V DC insulation test at 1 MΩ for 1 minute to earth.

Compliance and certification package

The drive carries UL 508C, IEC 61800-3 (EMC), IEC 61800-5-1 (safety), IEC 61000-3-12 (harmonic), IEC 60721-3 (environmental), IEC 61508 / IEC 13849-1 (functional safety). CE marked and TAA compliant.

Options and fieldbus integration

Three expansion slots (A, B, C) accept communication modules for PROFIBUS DP V1, PROFINET, DeviceNet, EtherCAT, CANopen, or Ethernet Powerlink. Encoder interface modules (digital 5/12 V, analog, resolver) fit slot B. Digital/analog I/O and relay extension modules use any slot. Built-in Ethernet/IP and Modbus TCP with half/full duplex and auto-negotiation at 10/100 Mbps.

Commissioning brief

Wall-mount oriented vertically ±10°. Ambient temperature 5-95% RH non-condensing. Altitude up to 1000 m full rating; derate 1% per 100 m to 4800 m. Vibration resistance 1.5 mm pk-pk at 2-13 Hz and 1 gn at 13-200 Hz. Shock 15 gn for 11 ms. Requires 600 m³/h cooling air.

Frequently asked questions

What is the phase configuration for this drive?

It is a 3-phase drive.

What are the control supply voltage requirements?

Digital inputs require external 24 V DC (19-30 V). Internal supplies provide 10.5 V DC for a reference potentiometer (1-10 kΩ) and 24 V DC (21-27 V) for digital inputs and STO. Insulation tested at 500 V DC for 1 minute.

What compliance documentation does this drive have?

It is UL 508C, IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1 certified, CE marked, and TAA compliant.